5.8

Re-initializing the SM-PROFIBUS DP-V1

Table 5.9 SM-PROFIBUS DP-V1
Pr MM.32
Changes to the SM-PROFIBUS DP-V1 configuration in menu 15, 16 and 17 parameters
will not take effect until the SM-PROFIBUS DP-V1 has been re-initialized.
To re-initialize SM-PROFIBUS DP-V1:
Set Pr MM.32 to ON.
When the sequence has been completed, Pr MM.32 will be reset to OFF.
The SM-PROFIBUS DP-V1 will re-initialise using the updated configuration.
This sequence does NOT store the SM-PROFIBUS DP-V1 configuration parameters in
NOTE
the drive or the SM-PROFIBUS DP-V1 FLASH memory. This will change back to 0
immediately and as such the change may not be visible on the display.
5.9

Re-initialize all Solutions Modules

To re-initialize all Solutions Modules fitted on a drive:
Set Pr xx.00 to 1070. (See note regarding Digidrive SK).
Reset the drive.
On Digidrive SK drives, Pr 00.00 is not available.
NOTE
This sequence does NOT store the SM-PROFIBUS DP-V1 configuration parameters in
NOTE
the drive or the SM-PROFIBUS DP-V1 FLASH memory.
5.10

Saving parameters to the drive

To avoid loss of the configured settings when the drive is powered down it is necessary
to write 1000 to Pr xx.00 followed by pressing the reset button to perform a drive save.
To store drive parameters:
Set Pr xx.00 to 1000. (See note regarding Digidrive SK).
Reset the drive.
On Digidrive SK drives, Pr 00.00 is not available.
NOTE
The drive will store all the drive parameters (except applications menu 20) but the
operation of the SM-PROFIBUS DP-V1 will not be affected. Any changes made to the
SM-PROFIBUS DP-V1 configuration parameters (mapping etc.) will not take effect until
the SM-PROFIBUS DP-V1 module is reset.
On drives with multiple option module slots, the applications menu 20 may be saved if
NOTE
an SM-Applications module is fitted, menu 20 is stored in the SM-Applications module's
memory. See the SM-Applications documentation for more information. If the drive is
running on backup supply only, Pr xx.00 must be set to 1001 to perform a save.
20
re-initialize
Default
0 (OFF)
Range
0 (OFF) to 1 (ON)
Access
RW