Table 14.4 Mapping error codes
Mapping
status
115
120
121
122
204
210
211
212
213
214
215
220
221
222
SM-PROFIBUS DP-V1 User Guide
Issue : a
Error
Description
Inter-option
A request to set up an inter-option communications block failed.
communications
Either the server does not support block transfer or parameters
error
were not legal.
Too many IN data
After expanding ranges of block mappings, too many IN cyclic data
objects mapped
channels configured.
Mapping over
Total size of all IN cyclic data mappings has exceeded the total
length
size of the cyclic data.
Register mode
More than ten cyclic IN data channels have been selected with
objects exceeded
direct data mapping mode.
A non-cyclic data mode has been mapped more than once in the
Multiple non-cyclic
OUT cyclic data mapping configuration parameters
mapping error
(Pr MM.20 to Pr MM.29)
Configuration read
An error has occurred reading the OUT cyclic data mapping
error
configuration parameters (Pr MM.20 to Pr MM.29) from the drive.
One or more parameters specified in the OUT cyclic data mapping
Invalid destination
configuration (Pr MM.20 to Pr MM.29) is outside of the allowed
parameter
range for PROFIBUS-DP. The allowable parameter range is from
Pr 0.00 to Pr 199.99.
One or more parameters specified in the OUT cyclic data mapping
configuration (Pr MM.20 to Pr MM.29) cannot be used as a
destination parameter for OUT data. The parameter may not exist,
or is a read-only parameter.
Write mismatch
This error will also occur if an attempt is made to map OUT data to
the configuration parameters of a fieldbus option in another slot,
unless that fieldbus is configured in register mode
i.e. Pr MM.09 = ON (1).
OUT data mapping parameters (Pr MM.20 to Pr MM.29) are not
Hole in OUT data
contiguous. It is not possible to have an unused parameter in the
mapping
configuration
middle of the cyclic data.
Two or more OUT cyclic data mapping configuration parameters
Duplicate mapping
(Pr MM.20 to Pr MM.29) have been configured with the same
error
destination parameter reference.
Inter-option
A request to set up an inter-option communications block failed.
communications
Either the server does not support block transfer or parameters
error
were not legal.
Too many OUT
After expanding ranges of block mappings, too many OUT cyclic
data objects
data channels configured.
mapped
Total size of all OUT cyclic data mappings has exceeded the total
Mapping over
length
size of the cyclic data.
Register mode
More than ten cyclic OUT data channels have been selected with
objects exceeded
direct data mapping mode.
www.leroy-somer.com