5.3

Set-up flow chart

Figure 5-1 Set-up flow chart
Connect all drives
together using
approved cable /
connectors / repeaters
Ensure all segments
correctly terminated
and termination
Ensure segment
lengths are no longer
than the maximum
Ensure a minimum
node to node cable
distance of 1m
Ensure no more than
32 devices per segment
(including repeaters)
Ensure there are no
more than 125
addressed devices on
the network
Perform cable tests
Configure each node
address on the system
(
SM-PROFIBUS DP-V1
Pr MM.03)
Ensure all third party
devices use the same
Perform a network scan
using the master or
SM-PROFIBUS DP-V1 User Guide
Issue : a
Start
See Section 4
See Section 4
powered
See Section 4
limits
See Section 4
See Section 4
See Section 4
See Section 5
See Section 5
data rate
tester
A
www.leroy-somer.com
Set data size on node
Reset and save
parameters (Pr
MM.32=1 & Pr xx.00 =
1000 + reset)
Set mapping
parameters in the drive
(Pr MM.10 - Pr MM.29)
Set data size in master
for each node (use
GSD file if required)
Map data to master
program variables
A dedicated
PROFIBUS-DP
Start master and ensure
tester is
there are no errors
recommended.
Check data flow in both
A dedicated
PROFIBUS-DP
tester is
recommended.
A
See Section 5
(Pr MM.05)
See Section 5
See Section 7
See master
documentation
and Section 6
See master
documentation
See master
documentation
See master
documentation
directions
End
17

Hide quick links:

Advertisement