Module Serial Number; Troubleshooting - Leroy-Somer digitax st User Manual

Sm-profibus dp-v1 solutions module for fieldbus communication
Table of Contents

Advertisement

.
Table 10.14 SM-PROFIBUS DP-V1 error codes
Error code
0
52
61
65
66
70
71
74
80
81
82
83
97
98
99
10.10

Module serial number

Table 10.15
Pr MM.35
The serial number is a loaded into the SM-PROFIBUS DP-V1 during manufacture and
cannot be changed. It contains the last six digits of the ten digit serial number on the
label.
10.11

Troubleshooting

In order to assist in configuring the network, the Diagnostic flow chart on page 60 could
be used.
SM-PROFIBUS DP-V1 User Guide
Issue : a
Fault
No error detected
User control word trip
Configuration error
Network loss
Critical link failure
FLASH transfer error
Invalid fieldbus specific
data
SM-PROFIBUS DP-V1
overtemperature
Inter-option
communication error
Communication error to
slot 1
Communication error to
slot 2
Communication error to
slot 3
Firmware incompatible
Internal watchdog error Internal error. Cycle power to the drive to reset from this trip.
Internal software error
Module serial number
Default
Range
Access
www.leroy-somer.com
Description
Indicates that the SM-PROFIBUS DP-V1 module is healthy.
It is possible to trip the drive externally via various
communication channels.
The TRIP bit has been set in the drive control word.
An invalid configuration has been detected.
Refer to Pr MM.49 for mapping error codes.
No new messages have been received for the specified
network loss trip time.
Internal error
The SM-PROFIBUS DP-V1 was unable to upload the
configuration parameters from its FLASH memory to the
drive.
SM-PROFIBUS DP-V1 has detected an invalid data record.
E.g. the stored I&M data has an invalid checksum.
If the temperature inside the SM-PROFIBUS DP-V1
°
exceeds 82
C, the SM-PROFIBUS DP-V1 will trip the drive.
An inter-option communications time-out has occurred, but
SM-PROFIBUS DP-V1 is unable to determine the reason for
the error.
(Not Digidrive SK)
Direct communications between the SM-PROFIBUS DP-V1
and an SM-Applications in another slot has timed out.
The hardware revision level does not support the installed
firmware version.
If DP-V1 functionality is required then replace the module
with a DP-V1 compatible module. If DP-V1 functionality is
not required then install firmware version V03.01.01 or
earlier.
If trip persists, replace the SM-PROFIBUS DP-V1.
N/A
32-bit
RO
59