Leroy-Somer digitax st User Manual page 57

Sm-profibus dp-v1 solutions module for fieldbus communication
Table of Contents

Advertisement

Table 10.11 Mapping error codes
Mapping
status
110
111
112
113
115
120
121
122
204
210
211
212
213
214
215
SM-PROFIBUS DP-V1 User Guide
Issue : a
Error
Configuration read error
Invalid source parameter
Read mismatch
Hole in IN data mapping
configuration
Inter-option communications
error
Too many IN data objects
mapped
Mapping over length
Register mode objects
exceeded
Multiple non-cyclic mapping
error
Configuration read error
Invalid destination parameter
Write mismatch
Hole in OUT data mapping
configuration
Duplicate mapping error
Inter-option communications
error
www.leroy-somer.com
Description
An error has occurred reading the IN cyclic data
mapping configuration parameters from the drive.
(Pr MM.10 to Pr MM.19)
One or more parameters specified in the IN cyclic data
mapping configuration (Pr MM.10 to Pr MM.19) is
outside of the allowed range for PROFIBUS-DP.
The allowable parameter range is from 0.00 to 199.99
One or more parameters specified in the IN cyclic data
mapping configuration (Pr MM.10 to Pr MM.19) cannot
be used as a source parameter for IN data. The
parameter may not exist.
IN cyclic data mapping parameters are not contiguous,
(Pr MM.10 to Pr MM.19). It is not possible to have an
unused parameter in the middle of the cyclic data.
A request to set up an inter-option communications
block failed. Either the server does not support block
transfer or parameters were not legal.
After expanding ranges of block mappings, too many
IN cyclic data channels configured.
Total size of all IN cyclic data mappings has exceeded
the total size of the cyclic data.
More than ten cyclic IN data channels have been
selected with direct data mapping mode.
A non-cyclic data mode has been mapped more than
once in the OUT cyclic data mapping configuration
parameters (Pr MM.20 to Pr MM.29)
An error has occurred reading the OUT cyclic data
mapping configuration parameters from the drive
(Pr MM.20 to Pr MM.29).
One or more parameters specified in the OUT cyclic
data mapping configuration is outside of the allowed
range for PROFIBUS-DP (Pr MM.20 to Pr MM.29).
The allowable parameter range is from 0.00 to 199.99
One or more parameters specified in the OUT cyclic
data mapping configuration (Pr MM.20 to Pr MM.29)
cannot be used as a destination parameter for OUT
data. The parameter may not exist, or is a read-only
parameter.
This error will also occur if an attempt is made to map
OUT data to the configuration parameters of a fieldbus
option in another slot, unless that fieldbus is configured
in register mode, i.e. Pr MM.09 = ON (1).
OUT data mapping parameters are not contiguous
(Pr MM.20 to Pr MM.29). It is not possible to have an
unused parameter in the middle of the cyclic data.
Two or more OUT cyclic data mapping configuration
parameters (Pr MM.20 to Pr MM.29) have been
configured with the same destination parameter
reference.
A request to set up an inter-option communications
block failed. Either the server does not support block
transfer or parameters were not legal.
57