11.9
PROFIdrive control word
The PROFIdrive control word consists of sixteen control bits some of which are
reserved.
Table 11.5 PROFIdrive control word bit functions
Bit
Value
0
1
2
3
4
5
6
7
8
9
10
11-15
68
Function
Description
1
No Ramp Stop Ramp Stop command is withdrawn.
The motor decelerates under ramp control using deceleration rate1
0
Ramp Stop
(Pr 2.21); inhibits the drive and go to 'Ready For Switching On'
state.
1
No Coast Stop Coast Stop command is withdrawn.
Voltage disconnected; inhibit the drive output stage. Main
0
Coast Stop
contactor is de-energized (if available), and the drive goes into the
'Switching On Inhibited' status: Motor coasts down
1
No Quick Stop Quick Stop command is withdrawn.
The motor decelerates under ramp control using deceleration rate2
0
Quick Stop
(Pr 2.22); inhibits the drive and go to 'Switching On Inhibited' state.
Enable
1
Enable the drive and accelerate to the specified set point.
Operation
Disable
Inhibit the drive. Drive coasts down (ramp-function generator to
0
Operation
zero or tracking), and into the Switched On' status.
1
Enable RFG
Enables the ramp function generator output.
Ramp function generator output is set to zero. Main contactor
0
Reset RFG
remains in, the drive is not isolated from the supply, drive ramps
down along the current limit or at the DC bus voltage limit.
1
Unfreeze RFG Unfreezes the ramp function generator output.
0
Freeze RFG
Freezes the current set point from the ramp function generator.
Enable
1
Selected value at the ramp function generator input is switched in.
Setpoint
Inhibit
0
Selected value at the ramp function generator input is set to 0.
Setpoint
Group signal is acknowledged at a positive edge; the drive is in the
Fault
1
'fault' status until the fault has been removed and then goes into
Acknowledge
'switch-on inhibit' state.
0
No meaning
Prerequisite: Operation is enabled and Main Setpoint=0. The drive
1
JOG1 ON
accelerates as fast as possible to jogging setpoint (Pr 1.05) in the
forward direction.
The drive brakes as fast as possible along the RFG, if 'JOG1' was
0
JOG1 OFF
previously ON, and goes into 'operation enabled' at standstill.
Prerequisite: Operation is enabled and Main Setpoint=0. The drive
1
JOG2 ON
accelerates as fast as possible to jogging setpoint (Pr 1.05) in the
reverse direction.
The drive brakes as fast as possible along the RFG, if 'JOG2' was
0
JOG2 OFF
previously ON, and goes into 'operation enabled' at standstill.
Network
Control from the PROFIBUS-DP network, process (
1
control
valid.
Process data invalid. Last received valid process data values are
0
No control
retained.
0
Reserved
www.leroy-somer.com
SM-PROFIBUS DP-V1 User Guide
cyclic
) data is
Issue : a