5.6

Data format

Table 5.5 PROFIBUS-DP
Pr MM.05
The default data format is four cyclic words, each cyclic data channel is mapped to a
drive parameter. The default mappings are shown in Table 5.6.
The maximum number of 16-bit data words that is possible is 32 with only cyclic data, 31
NOTE
with Mode 1 non-cyclic data and 28 with PPO4 word mode.
Table 5.6 Default data mapping
Cyclic word
IN channel 0
IN channel 1
OUT channel 0
OUT channel 1
Other data formats are also supported. For further details see section 7.2 Data
formats on page 24. The directions specified in Table 5.6 relate to the data direction as
seen by the master.
5.7

Network operating status

Table 5.7
Pr MM.06
The PROFIBUS-DP network activity can be monitored in the SM-PROFIBUS DP-V1
operating status parameter, Pr MM.06. When the SM-PROFIBUS DP-V1 is
communicating successfully with the PROFIBUS-DP master controller, Pr MM.06 will
give an indication of the number of cyclic data messages that are being processed per
second. This parameter is also available in menu 0 on the Digidrive SK (Pr 00.54).
Table 5.8 Network operating status codes
Pr MM.06
>0
0
-1
-2
-3
If a mapping configuration error (see section 10.7 Mapping status ) or network error
(see section 10.9 Module error code ) is detected, the drive may trip.
SM-PROFIBUS DP-V1 User Guide
Issue : a
data format
Default
Ranges
Access
Data word
word 0, 1
word 2, 3
word 0, 1
word 2, 3
Network operating status
Default
Range
Access
Parameter
Description
Network healthy
Indicates the number of processed cyclic messages per second.
Indicates that the PROFIBUS-DP master has established
communications with the SM-PROFIBUS DP-V1. If operating
Network healthy,
status changes briefly to -1 and returns to 0, the slave
no data transfer
configuration does not match the configuration in the master
controller.
Indicates that the SM-PROFIBUS DP-V1 has initialized correctly,
Initialised
and is waiting for the PROFIBUS-DP master to initialize
communications.
Indicates that part of the SM-PROFIBUS DP-V1 initialisation
Internal hardware
sequence was not successful. If this fault persists after a power
failure
cycle, replace the SM-PROFIBUS DP-V1.
Indicates an invalid setting in the SM-PROFIBUS DP-V1
Configuration error
configuration parameters. Parameters Pr MM.49 and Pr MM.50 will
contain additional information.
www.leroy-somer.com
4
0 to 32,100 to 131, 200 to 228
RW
Default mapping status
Pr 10.40, status word
Pr 2.01, post-ramp speed reference
Pr 6.42, control word
Pr 1.21, digital speed reference 1
N/A
-3 to 9999
RO
19