5.4

Node address

Table 5.2 PROFIBUS-DP
Pr MM.03
Every node on a PROFIBUS-DP network must be given a unique network node
address. To activate a change in the node address value the SM-PROFIBUS DP-V1
must be re-initialized (Pr MM.32 = ON). This parameter is also available in menu 0 on
the Digidrive SK (Pr 00.52). Addresses 0 and 126 are reserved for system use.
5.5

Network data rate

Table 5.3 PROFIBUS-DP
Pr MM.04
The SM-PROFIBUS DP-V1 will automatically detect the PROFIBUS-DP network data
rate and synchronize to it. Pr MM.04 will indicate the data rate that has been detected
by the SM-PROFIBUS DP-V1. This parameter is also available in menu 0 on the
Digidrive SK (Pr 00.53).
A value of -1 indicates that the SM-PROFIBUS DP-V1 has not detected any activity on
the PROFIBUS-DP network, and is waiting for the master controller to start
communicating.
The PROFIBUS-DP data rate parameter can be changed, but this will not affect the data
NOTE
rate at which the SM-PROFIBUS DP-V1 communicates. The data rate display will be
updated when SM-PROFIBUS DP-V1 is re-initialized.
Table 5.4 Network data rate status
Pr MM.04
18
node address
Default
Range
Access
data rate
Default
Range
Access
-1
0
1
2
3
4
5
6
7
8
9
www.leroy-somer.com
126
0 to 126
RW
N/A
-1 to 9
RO
bit/s
Auto-detecting
12M
6.0M
3.0M
1.5M
500k
187.5k
93.75k
45.45k
19.2k
9.6k