Table 10.11 Mapping error codes
Mapping
status
220
221
222
10.8

Drive trip display codes

If the SM-PROFIBUS DP-V1 detects an error during operation, it will force a trip on the
drive. However, the trip code displayed on the drive will only indicate which slot initiated
the trip. The exact reason for the trip will be indicated in the SM-PROFIBUS DP-V1 error
code parameter, Pr MM.50.
Table 10.12 shows the possible trip codes that will be displayed on the drive when a
problem is detected with the SM-PROFIBUS DP-V1 or when the SM-PROFIBUS DP-V1
initiates a trip.
Table 10.12 Drive trip display codes
Trip
Code
SLX.HF
SLX.Er
SLX.nF
SLX.dF
Digidrive SK will show SL.Er without a slot number.
NOTE
10.9

Module error code

Table 10.13
Pr MM.50
If the SM-PROFIBUS DP-V1 detects an error during operation, it will force a trip on the
drive and update the error code parameter, Pr MM.50. Table 10.14 shows the possible
SM-PROFIBUS DP-V1 error codes
58
Error
Too many OUT data objects
mapped
Mapping over length
Register mode objects
exceeded
Fault
Description
Hardware
The drive has detected that a Solutions Module is
fault
present, but is unable to communicate with it.
Error
User trip generated by the SM-PROFIBUS DP-V1
This trip will occur if a drive slot was previously
Not fitted
configured with an options module but on power up,
no options module was detected.
The slot configuration parameters stored in the drive
Different
are not valid SM-PROFIBUS DP-V1 configuration
module
parameters.
fitted
This trip will also occur if an SM-PROFIBUS DP-V1
module is fitted to a previously unused slot.
Module error code
Default
Range
Access
www.leroy-somer.com
Description
After expanding ranges of block mappings, too many
OUT cyclic data channels configured.
Total size of all OUT cyclic data mappings has
exceeded the total size of the cyclic data.
More than ten cyclic OUT data channels have been
selected with direct data mapping mode.
N/A
0 to 255
RO
SM-PROFIBUS DP-V1 User Guide