Kind
OFF
Setpoint turned off/ignored.
GROSSSP
Gross setpoint. Trips when the current gross weight matches this value.
NETSP
Net setpoint. Trips when the current net weight matches this value.
+RELSP
Positive relative setpoint. Trips at a specific value above the referenced setpoint.
–RELSP
Negative relative setpoint. Trips at a specific value below the referenced
setpoint.
%RELSP
Percent relative setpoint. Trips at a specific percentage value of the referenced
setpoint.
Discontinued Product
PAUSE
Pauses the batch sequence indefinitely. Operator must activate the BATSTRT
digital input to continue processing.
DELAY
Delays the batch sequence for a specified time. The length of the delay (in
tenths of a second) is specified on the Value parameter.
WAITSS
Wait for standstill. Pauses the batch sequence until the scale is at standstill.
COUNTER
Specifies the number of consecutive batch sequences to perform.
AUTOJOG
Automatically jogs the previous filling operation.
COZ
Center of zero. The digital output associated with this setpoint is activated
when the scale is at center of zero. No value is required for this setpoint.
INMOTON
In motion. The digital output associated with this setpoint is activated when the
scale is not at standstill. No value is required for this setpoint.
INRANGE
In range. The digital output associated with this setpoint is activated when the
scale is within capacity range. No value is required for this setpoint.
–GROSS
Negative gross weight. The digital output associated with this setpoint is
activated when the gross weight reading is less than zero. No value is required
for this setpoint.
–NET
Negative net weight. The digital output associated with this setpoint is activated
when the net weight reading is less than zero. No value is required for this
setpoint.
BATCHPR
Batch processing signal. The digital output associated with this setpoint is
activated whenever a batch sequence is in progress. No value is required for
this setpoint.
TIMER
Tracks the progress of a batch sequence based on a timer.
The timer value, specified in tenths of a second on the VALUE parameter,
determines the length of time allowed between start and end setpoints. The
indicator START and END parameters are used to specify the start and end
setpoints. If the END setpoint is not reached before the timer expires, the digital
output associated with this setpoint is activated.
CONCUR
Allows a digital output to remain active over a specified portion of the batch
sequence. Two types of concur setpoints can be configured:
Type 1 (VALUE=0): The digital output associated with this setpoint becomes
active when the START setpoint becomes the current batch step and remains
active until the END setpoint becomes the current batch step.
Type 2 (VALUE > 0): If a non-zero value is specified for the VALUE parameter,
that value represents the timer, in tenths of a second, for this setpoint. The
digital output associated with this setpoint becomes active when the START
setpoint becomes the current batch step and remains active until the timer
expires. NOTE: If more than one concurrent setpoint is configured, each must
be assigned to a different digital output.
56
IQ Plus 710 Installation Manual
Description
Table 8-1. Setpoint Kinds