Power Cabling; Ac Powered Nodes; Dc Powered Nodes; Lm-Bcc Cabling - Cisco BPX 8620 Installation And Configuration Manual

Hide thumbs Also See for BPX 8620:
Table of Contents

Advertisement

Power Cabling

Power Cabling
Power connections are made to the AC Power Supply Shelf or the DC Power Entry Module at the rear
of the BPX switch. For acceptable cable and wire types, see Table 31-2 and Table 31-3.

AC Powered Nodes

AC power cables may be provided by you or ordered from Cisco. Several standard cables are available
(see Table 31-2). AC cables with other plugs or different lengths may be special ordered.
For those who wish to construct their own power cable, the cable must mate with an IEC320 16/20A
male receptacle on the rear of the AC Power Supply Assembly.

Table 31-2 AC Power Cables

Cable Parameter
Cable:
Plug: customer end

DC Powered Nodes

DC wiring is generally provided by the customer. Table 31-3 lists the cable parameters.

Table 31-3 DC Power Wiring

Cable Parameter
Wiring:
Connection:

LM-BCC Cabling

LM-BCC cabling connects data ports on the LM-BCC to control terminals and modems. It is also used
for external clock inputs from a clock source.
See for more details on peripherals that can be attached to these ports.

Auxiliary and Control Port Cabling

The auxiliary and control ports are used to connect one of the nodes in the network to a control terminal
or modem connections for remote alarm reporting or system monitoring. For details on this cable, see
Table 31-4 and Table 31-5.
Cisco BPX 8600 Series Installation and Configuration
31-2
Description
Provided with 8 feet (2.3 m.) of 3-conductor wire with plug.
20 A NEMA L620, 3-prong plug (domestic) or
13 A 250 Vac BS1363, 3-prong fused plug (UK, Ireland)
CEE 7/7 (Continental Europe)
AS3112 (Australia/New Zealand)
CEI23-16/VII (Italy)
Description
Single conductor, 8 AWG recommended wire gauge, 75°C insulation rating,
copper conductors only. Provision is provided for attaching conduit.
90° ring lug for #10 screw terminal block.