Packet Elements - Mitsubishi Electric QJ71E71-100 User Manual

Q corresponding ethernet interface module
Table of Contents

Advertisement

11.3

Packet Elements

A packet consists of packet elements.
Up to 32 elements can be placed in a packet, and the maximum data length is 2046 bytes per packet.
The following shows the details of the packet elements.
For examples of packet element data, refer to Page 386, Appendix 8.3.
(1) Static Data
This element is used when a specific code or character string such as a command exists in a packet.
• When sending: The specified code and character string are sent.
• When receiving: Receive data are verified.
Multiple Static Data elements can be placed anywhere in the data part.
The following table lists the items.
Item
Element Name
Code Type
Setting Value
CHAPTER 11 DATA COMMUNICATIONS USING THE PREDEFINED PROTOCOL
Description
Set name of the element.
Select a data type of the setting value.
ASCII String/ASCII Control Code/HEX
Set data within 1 to 50 bytes.
Code type and setting range are as follows:
• ASCII String: 20
to 7F
H
H
• ASCII Control Code: Control code of 00
• HEX: Hexadecimal data of 00
to 1F
and 7F
H
H
H
to FF
H
H
Remark
-
-
Setting example
ASCII String: "ABC"
ASCII Control Code: STX
HEX: FFFF
117
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qj71e71-b5Qj71e71-b2

Table of Contents