(2) Control data
Device
(S1)+0
(S1)+1
(S1)+2
(S1)+3
(S1)+4
to
(S1)+7
(3) Functions
• This instruction turns off the COM.ERR. LED and clears error information listed below for the module
specified by Un.
Initial error
Open error
Error log
Communication
status
All
270
Item
System area
Stores the status at completion.
0000
Completion status
Values other than 0000
Abnormal end
Specify error information to be cleared.
0000
0001
connection with the connected device
0100
0101
Clear target
specification
protocol
0102
receiving status
0103
status
FFFF
Specify the function to be cleared.
Clear function
0000
specification
FFFF
System area
Item
specification
0001
Status for each
protocol
E-mail receiving
status
E-mail sending
status
Setting data
-
: Normal completion
H
(error code):
H
: Initial error code
H
to 0010
: Open error code for a
H
H
: Error log block area
H
: Communication status - status for each
H
: Communication status - e-mail
H
: Communication status - e-mail sending
H
: Clears all of the above
H
: COM.ERR LED off, error code clear
H
: Error log clear
H
-
Target
Function
specification
(S1)+2
(S1)+3
0000
0000
H
H
to 0010
0000
H
H
H
0100
FFFF
H
H
0101
FFFF
H
H
0102
FFFF
H
H
0103
FFFF
H
H
FFFF
FFFF
H
H
Setting range
-
-
As described in
the left
0000
,
H
FFFF
H
-
Error information to be cleared
(buffer memory)
• Initial error code (address: 69
• COM.ERR. LED off
• Open error code for a connection with the
connected device (address: 7C
Error log (address: E3
to 174
H
Clears communication status.
(address: 178
to 1FF
)
H
H
E-mail receiving
(address: 5871
to 5B38
)
H
H
E-mail sending
(address: 5B39
to 5CA0
)
H
H
Clears all of the above.
Set by
-
System
User
User
-
)