Error
code
• The setting value of the default router IP address for
the router relay function is incorrect.
• The network address (network address after the
C005
H
subnet mask) of the default router IP address is
different from that of the IP address of the Ethernet
module in the own station.
The setting value of the subnet address for the router
C006
H
relay function is incorrect.
• The setting value of the router IP address for the
router relay function is incorrect.
• The network address (network address after the
C007
H
subnet mask) of the router IP address is different from
that of the IP address of the Ethernet module in the
own station.
The setting value in IP filter function type setting
C008
H
(address: 5701
) is not correct.
H
• A value out of range is set in IP address setting 1 to 8
(address: 5702
C009
• In IP address setting 1 to 8 (address: 5702
H
5721
), the value of start IP address is greater than
H
the end IP address.
The send/receive process has been executed while the
C00E
H
IP address in use detection function is being executed.
C00F
One IP address is used for two or more modules.
H
The setting value of the Ethernet module port number
C010
H
for the open process is incorrect.
The setting value of the port number of the connected
C011
H
device for the open process is incorrect.
The port number set is used in a connection already
C012
H
opened in TCP/IP.
The port number used in a connection already opened
C013
H
is set for the open process in UDP/IP.
The initial process or open process of the Ethernet
C014
H
module is not completed.
The setting value of the IP address of the connected
C015
H
device for the open process is incorrect.
The open process of the connection (or the next
C016
connection) specified for pairing open has been already
H
completed.
A connection could not be established in the open
C017
H
process of the TCP connection.
314
Error description
to 5721
).
H
H
H
• Correct the default router IP address and perform the initial
process again.
• Set the same network address as that of the IP address of the
Ethernet module in the own station.
• Correct the subnet address and perform the initial process again.
• Correct the router IP address and perform the initial process again.
• Change the IP address of the Ethernet module in the own station
to the same address as the network address.
Correct the value in IP filter function type setting (address: 5701
and perform IP filter setting by the reinitialization process again.
Correct the values in IP address setting 1 to 8 (address: 5702
to
5721
) and perform IP filter setting by the reinitialization process
H
again.
Do not execute the send/receive process while executing the IP
address in use detection function.
• Set different IP addresses.
The MAC addresses of the Ethernet modules in the stations with the
same IP address can be checked in IP address status storage area
(5281
to 5286
).
H
H
• Correct the port number.
• Correct the port number.
• Correct the port numbers of the Ethernet module and the
connected device.
• Correct the port number of the Ethernet module.
• Perform the initial process or open process.
• Correct the IP address. Set the class to A/B/C.
• Check that none of the connections targeted for pairing open has
been opened.
• Correct the combination of modules set for pairing open.
• Check the operation of the connected device.
• Check the open process of the connected device.
• Correct the open setting of the communication parameters.
• Correct the port number of the Ethernet module, the IP address
and port number of the connected device, and the open setting.
• Check if the cable is disconnected.
• Check if there is a problem with the connection to the transceiver
or terminating resistor.
Action
)