12.5.1

Parameter setting when using an interrupt program

Configure the parameter setting on a programming tool to start up an interrupt program.
Connection No.1
Connection No.2
Connection No.16
(1) Interrupt pointer setting
The following is a setting example.
Project window
Item
Interrupt Pointer Start No.
PLC Side
Interrupt Pointer Count
Start I/O No.
Intelligent Module
Side
Start SI No.
E71
Control
number
interrupt
(SI) No.
Setting
0
of (2)
to
15
[Parameter]
Set the start number of the interrupt pointer used in a
program.
Set the number of interrupt pointers used in a program.
Set the start I/O number of an E71.
Among maximum 16 interrupt (SI) numbers (control numbers
on the Ethernet module side) to be set in the interrupt
program, set the smallest numbers 0 to 15.
CHAPTER 12 COMMUNICATIONS USING A FIXED BUFFER
<Program>
Interrupt
pointer
Setting
(Ixx)
of (1)
50
to
255
[PLC Parameter]
[PLC System]
Description
CPU module
Ixx
Z.BUFRCVS
button
Setting range
50 to 255
1 to 16
0000
to 0FE0
H
0 to 15
12
H
149