PART II. Programming the parameters for CA60Plus alarm
Carefully study this installation manual before programming the alarm station.
The respective parameters can be configured from a keyboard or remote control connected to the
system – a personal computer via a telephone using the UDLManager program.
Keyboard programming:
The CA60Plus Alarm System engineer parameters programming mode can be only begin when the
system is in disarmed mode.
Keying in the system engineer code will initiate the CA60Plus Alarm System programming mode for
the engineer parameters. After restoring the default parameters (RESET) the engineer code will remain
7777.
The respective Alarm System parameters can be programmed after a double-digit address is intro-
duced. Use the table with addresses in Supplement A and the detailed instructions about the addresses in
the remaining part of the manual.
The table with addresses provides the system RESET configuration.
A detailed description of the possible parameters, the keypad display indicators and the necessary
programming functions has been provided for each address.
Each address has been provided default configurations after a software or hardware RESET has been
carried out.
The information entered for each address can be confirmed by pressing the ENTER button.
When reviewing the programmed parameters it is recommended to exit any given address by single
pressing the CLEAR button. This function will leave the introduced parameters unchanged.
In case the programmer is disoriented in the engineer menu, it is recommended to exit the menu by
double clicking the CLEAR button and to begin programming the station parameters from the start.
Remote programming using the UDLManager program
To access a UDLManager program system requires a system password and a station program pass-
word. After restoring the default parameters these passwords will be the same and are 1234. In order to
provide access to the system from the central station enter the correct password of the central station at
Address 71.
A 24-hour period automatically begins after default parameters are restored during which the system
is in remote programming standby mode. Following this period, the "ring number" parameter is zeroed,
whereby the system will be locked for remote programming. This 24-hour period can be canceled by
introducing a telephone number for connecting to the central station at Address 70.
Detailed working instructions for the UDLManager program are provided in the built-in Help files.
The details listed in this manual apply to all parameters for remote system programming.
14
control panel
CA60Plus control panel Installation manual