Fig. 9 Connecting a key-switch and a fire detector with relay in the base
to a CA60Plus control panel
10
ZONE x
Must be normally closed.
COM
TAMPER
ZONE
Tamper switch of the key-switch.
COM
Connecting key-switch with one balancing resistor
ZONE x
Must be normally closed.
COM
Tamper switch of the key-switch.
Connecting keyswitch with two balancing resistors
COM
Z2
SIREN
PGM3
PGM2
PGM1
+PGM
-AUX
+AUX
AC
CA60Plus
Connecting a fire detector with a relay in the base
in scheme with one balancing resistor
COM
Z2
SIREN
PGM3
PGM2
PGM1
+PGM
-AUX
+AUX
AC
CA60Plus
Connecting a fire detector with a relay in the base
in scheme with two balancing resistors
NC
Key-switch
NC
1k
NC
Key-switch
NC
The programmable output
must be programmed
as Fire Reset and the active
1k
status must be +12 VDC.
COM
NC
NO
GND
+12 V
Fire
detector
base
The programmable output
must be programmed
as Fire Reset and the active
1k
status must be +12 VDC.
1k
COM
NC
NO
GND
+12 V
Fire
detector
base
CA60Plus control panel Installation manual
1k
1k
1k