Start Up / Engine Alarms - Carrier VECTOR 6500 Operation & Service Manual

Single-temp trailer and rail refrigeration units with advancet microprocessor
Table of Contents

Advertisement

Alarm
Steps
NO.
30
FAILED TO RUN MINIMUM TIME
TRIGGER–ON: The unit has shutdown on an alarm 3 times without having run for at least 15
minutes between each shutdown (not including Door shutdowns.)
UNIT CONTROL:
RESET CONDITION: Alarm may be manually reset via keypad or by turning the unit off, then back on
again. If the Unit Operation configuration is set to Rail Mode, this alarm will reset after 4 hours.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 page 7−2.) Operate the unit through the appropriate modes to see if any active alarm
occurs. Continue with the steps below as necessary.
Check For Alarms
Check for shutdown alarms.
62-11389
Alarm/Cause

7.5 START UP / ENGINE ALARMS

Engine Operation: engine and unit shutdown and alarm.
Standby Operation: refrigeration system shutdown and alarm with PSCON
still energized.
7−22
Corrective Action
Alarm conditions must be corrected and the alarm(s)
cleared to continue.