Carrier VECTOR 6500 Operation & Service Manual page 232

Single-temp trailer and rail refrigeration units with advancet microprocessor
Table of Contents

Advertisement

Alarm
Steps
NO.
225
GENERAL MAINTENANCE DUE
TRIGGER–ON: The General Maintenance Hour Meter time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
2
Perform Maintenance
Perform appropriate engine & unit
maintenance.
3
Reset General Maintenance Hour Meter
a. Check
Maintenance Hour Meter interval is
set for your requirements.
b. Reset General Maintenance Hour
Meter for the next service interval.
226
SERVICE SOON-PM #1 DUE
TRIGGER–ON: The Maintenance Hour Meter #1 time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
2
Perform Maintenance
Perform appropriate engine & unit
maintenance.
3
Reset Maintenance Hour Meter #1
a. Check that Maintenance Hour
Meter #1 interval is set for your
requirements.
b. Reset Maintenance Hour Meter #1
for the next service interval.
Alarm/Cause
that
the
General
7−99
Corrective Action
Must be done soon!
Follow instructions on proper maintenance form.
Reset configured Interval if required.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.
Must be done soon!
Follow instructions on proper maintenance form.
Reset configured Interval if required.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.
62-11389