Page 1
Container Refrigeration OPERATION AND SERVICE 69NT40- -511- -300 to 399 (excluding --310, --344 & --359) Container Refrigeration Units T--285 Rev G...
Page 2
OPERATION AND SERVICE MANUAL CONTAINER REFRIGERATION UNIT 69NT40--511--300 to 399 (excluding --310, --344 & --359)
Page 3
SAFETY SUMMARY GENERAL SAFETY NOTICES The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. The general safety notices are presented in the following three sections labeled: First Aid, Operating Precautions and Maintenance Precautions.
Page 4
SPECIFIC WARNING AND CAUTION STATEMENTS - - Continued WARNING Make sure that the unit circuit breaker(s) (CB-1 & CB-2) and the START-STOP switch (ST) are in the “O” (OFF) position before connecting to any electrical power source. WARNING Never use air for leak testing. It has been determined that pressurized, mixtures of refrigerant and air can undergo combustion when exposed to an ignition source.
Page 5
The set screw on the crankshaft must be removed for this type of oil pump. CAUTION Use only Carrier Transicold approved Polyol Ester Oil (POE) - - Mobil ST32 compressor oil with R-134a. Buy in quantities of one quart or smaller. When using this hygroscopic oil, immediately reseal.
Page 6
SPECIFIC WARNING AND CAUTION STATEMENTS - - Continued CAUTION Take necessary steps (place plywood over coil or use sling on motor) to prevent motor from falling into condenser coil. CAUTION If the thermostatic expansion valve is found to be in need of replacement, then the power head and cage assembly are to replaced as a pair.
Page 7
TABLE OF CONTENTS PARAGRAPH NUMBER Page GENERAL SAFETY NOTICES ............Safety-1 FIRST AID .
Page 12
LIST OF ILLUSTRATIONS FIGURE NUMBER Page Figure 2-1 Refrigeration Unit -- Front Section ........... . . Figure 2-2 Evaporator Section .
Page 13
LIST OF ILLUSTRATIONS (continued) FIGURE NUMBER Page Figure 6-25 Jumper Assembly ..............6-18 Figure 6-26 Controller Section of the Control Box .
Page 14
LIST OF TABLES TABLE NUMBER Page Table 2-1 Safety and Protective Devices ............Table 3-1 Key Pad Function .
Page 15
18 and 24 volts, single phase. The unit may be fitted with suction and discharge pressure gauges or suction and discharge transducers The controller is a Carrier Transicold Micro-Link 2i or no pressure readout. The transducer readings may microprocessor.
Page 16
(attached to the condenser coil cover). 1.3.26 Humidification The unit may be equipped with the Carrier Transicold 1.3.16 Thermometer Port NatureFresh humidity management system. The system includes a water tank, water pump, water heater...
Page 17
The identification label on each controller will have the digit dash number. See the unit identification Matrix part number as shown above followed by a dash and found Carrier site, then a blank space to allow the final dash number to be www.container.carrier.com.
SECTION 2 DESCRIPTION 2.1 GENERAL DESCRIPTION evaporator coil heaters. The unit model number, serial number and parts identification number can be found on 2.1.1 Refrigeration Unit - - Front Section the serial plate to the left of the compressor. The unit is designed so that the majority of the 2.1.2 Fresh Air Makeup Vent components are accessible from the front, see Figure 2-1.
2.1.3 Evaporator Section The evaporator fans circulate air through the container by pulling it in the top of the unit, directing it through the The evaporator section (Figure 2-2) contains the evaporator coil, where it is heated or cooled, and temperature recorder bulb or return recorder sensor, discharging it at the bottom.
2.1.4 Compressor Section modulating valve stepper motor drive, discharge pressure regulator valve discharge/suction The compressor section includes the compressor (with pressure transducers. high pressure switch), power cable storage The supply temperature sensor, supply recorder sensor compartment, and autotransformer. and ambient sensor are located at the right side of the This section also contains the suction modulating valve, compressor.
2.1.5 Air Cooled Condenser Section line valve, filter-drier, condenser pressure transducer and fusible plug. The air cooled condenser section (Figure 2-4) consists The condenser fan pulls air in the bottom of the coil and it of the condenser fan, condenser coil, receiver with sight is discharged horizontally out through the condenser fan glass/moisture indicator, quench valve, manual liquid grille.
2.1.6 Water-Cooled Condenser Section quench expansion valve, rupture disc, condenser pressure transducer, filter-drier, water couplings and The water-cooled condenser section (Figure 2-5) water pressure switch. The water cooled condenser consists of a water-cooled condenser, sight glass, replaces the standard unit receiver. Sight Glass Liquid Line Service Valve Water-Cooled Condenser...
2.1.7 Control Box Section 2.1.8 Communications Interface Module The control box (Figure 2-6) includes the manual The communications interface module is a slave operation switches; circuit breaker (CB-1); compressor, module which allow communication with a master fan and heater contactors; control power transformer; central monitoring station.
2.2 REFRIGERATION SYSTEM DATA Number of Cylinders Model 06DR Weight (Dry) 118 kg (260 lb) a Compressor/Motor a. Compressor/Motor Approved Oil Mobil ST32 Assembly Assembly Oil Charge 3.6 liters (7.6 U.S. pints) The oil level range, with the compressor off, should be between the bottom and one-eighth Oil Sight Glass level of the sight glass.
2.3 ELECTRICAL DATA CB-1 Trips at 29 amps CB-2 (50 amp) Trips at 62.5 amps a. Circuit Breaker a. Circuit Breaker CB-2 (70 amp) Trips at 87.5 amps 17.6 amps @ 460 vac b. Compressor Full Load Amps (FLA) Motor (with current limiting set at 21 amps) 380 vac, Single Phase, 460 vac, Single Phase,...
Orange wire Power Red wire Output Brown wire Ground Input voltage 5 vdc Output voltage 0 to 3.3 vdc i. Humidity Sensor Humidity Sensor Output voltage readings verses relative humidity (RH) percentage: 0.99 V 1.65 V 2.31 V 2.97 V j.
2.5 REFRIGERATION CIRCUIT outlet. The valve maintains a constant superheat at the coil outlet regardless of load conditions. Starting at the compressor, (see Figure 2-7 upper During periods of low load, the suction modulating valve schematic) the suction gas is compressed to a higher decreases flow of refrigerant to the compressor.
SECTION 3 MICROPROCESSOR 3.1 TEMPERATURE CONTROL MICROPRO- and cargo temperature parameters for future retrieval. CESSOR SYSTEM Coverage of the temperature control software begins with paragraph 3.2. Coverage of the DataCORDER The temperature control Micro-Link 2i microprocessor software is provided in paragraph 3.6. system (see Figure 3- 1) consists of a key pad, display module, control module (controller) and interconnecting wiring.
3.1.1 Key Pad Table 3-1 Key Pad Function The key pad (Figure 3- 2) is mounted on the right-hand FUNCTION side of the control box. The key pad consists of eleven push button switches that act as the user’s interface Code Select Accesses function codes.
Mounting Screw Fuses Micro-Link 2i Control Circuit Power Connection Controller (Location: In back of controller) Connectors Software Programming Port Test Points Battery Pack Figure 3- 4 Micro-Link 2i Controller 3.1.3 Controller f. Provide the ability to reprogram the software through the use of a memory card.
Software will change if any one of the inputs changes. current draw. The factory default allows on demand Overall interaction of the inputs is described as a “mode” starting of units and full current draw. Refer to Table 3-5. of operation. The modes of operation include, 3.3.6 Condenser Pressure Control perishable (chill) mode and frozen mode.
de-energize when the temperature rises to 0.2_C humidity. When the relative humidity sensed is 2% (0.4_F) below the set point. The compressor will not below the set point , the controller de-energizes the heat restart until the temperature rises to 0.2_C (0.4_F) relay.
3.3.12 Temperature Control - - Frozen Mode 3.4 CONTROLLER ALARMS With configuration variable CnF26 set to --10_C the Alarm display is an independent controller software frozen mode of operation is active with set points at or function. If an operating parameter is outside of below - -10_C (+14_F).
Function Codes. There are 35 functions (see used with the Carrier Transicold Data Reader to down Table 3-8, page 3-25) which the operator may access to load data. A personal computer with Carrier Transicold examine the current input data or stored data.
3 USDA thermistor inputs 7 sensors configuration to generic and selecting which data points (dCF02=64) 1 humidity input to record may be done using the Carrier Transicold Data 1 cargo probe (thermistor input) Retrieval Program. 2 thermistor inputs(supply & return) 1. Control mode...
Raw Data Report for ABC1234567 May 31, 2001 to Jun 04, 2001 System Configuration at the Time of Interrogation: Interrogated On Sept 05, 2001 Extracted by DataLine Rev 1.0.0 Controller Software: 5120 Controller Serial #: 04163552 Bill of Lading #: 1 Origin: Origin Date: Destination:...
If the probes are configured to AUTO, they act as a group. This function is designed to assist users who The Carrier Transicold Data Reader (see Figure 3- 6) is keep their DataCORDER configured for USDA a simple to operate hand held device designed to extract recording, but do not install the probes for every trip.
In response to the demand to replace fumigation with this environmentally sound process, Carrier has e. To initiate USDA Recording, connect the personal integrated...
“AA##,” if the alarm is active, where ## is the alarm 1. Press the ALT. MODE & ALARM LIST keys. number. “IA##,” will show if the alarm is inactive 2. Press the UP/DOWN ARROW key until “CLEAr” is displayed. d. “END” is displayed to indicate the end of the alarm list if any alarms are active.
Table 3-5 Controller Function Codes (Sheet 1 of 4) Code TITLE DESCRIPTION Note: If the function is not applicable, the display will read “-- -- -- -- -- ” Display Only Functions Displays the SMV percent open. The right display reads 100% when the valve is Cd01 Suction Modulation fully open and 0% when the valve is fully closed.
Page 43
Table 3-5 Controller Function Codes (Sheet 2 of 4) Cd22 Compressor Speed The status of the compressor is displayed (high, low or off). Cd23 Evaporator Fan Displays the current evaporator fan state (high, low or off). Cd24 Controlled Not used in this application Atmosphere State Compressor Run This code displays the time remaining until the unit goes into defrost (in tenths of...
Page 44
Table 3-5 Controller Function Codes (Sheet 3 of 4) The stagger start offset time is the amount of time that the unit will delay at start- Cd31 Stagger Start Offset up, thus allowing multiple units to stagger their control initiation when all units are Time (Seconds) powered up together.
Page 45
Table 3-5 Controller Function Codes (Sheet 4 of 4) Display Only Functions - - Continued Code Cd38 will display the current secondary supply temperature sensor reading Cd38 Secondary Supply for units configured for four probes. If the unit is configured with a DataCORDER, Cd38 will display “-- -- -- -- -- .”...
Page 46
Figure 3- 1Table 3-6 Controller Alarm Indications (Sheet 1 of 3) Code TITLE DESCRIPTION Alarm 11 is applicable to units with Single Evaporator Fan Capability (CnF32 set AL11 Evaporator Motor 1 to 1EFO) only. The alarm is triggered if the evaporator fan motor #1 internal pro- IP Trip tector opens.
Page 47
Table 3-6 Controller Alarm Indications (Sheet 2 of 3) Alarm 53 is caused by the battery pack charge being too low to provide sufficient power for battery-backed recording. Renew replaceable batteries. If this alarm AL53 Battery Pack Failure occurs on start up, allow a unit fitted with rechargeable batteries to operate for up to 24 hours to charge rechargeable batteries sufficiently to deactivate the alarm Alarm 54 is activated by an invalid primary supply temperature sensor reading that is sensed outside the range of --50 to +70_C (--58_F to +158_F) or if the...
Page 48
Table 3-6 Controller Alarm Indications (Sheet 3 of 3) Alarm 64 is triggered if the discharge temperature sensed is greater than 135_C AL64 Discharge Tempera- (275_F) for three continuous minutes, if it exceeds 149_C (300_F), or if the sen- ture Over Limit sor is out of range.
Table 3-7 Controller Pre-Trip Test Codes (Sheet 1 of 4) Code TITLE DESCRIPTION NOTE “Auto” or “Auto1” menu includes the: P, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu in- cludes P, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts.“Auto3 menu includes P, P1, P2, P3, P4, P5, P6, P7, P8 and rSLts All lights and display segments will be energized for five seconds at the start of Pre-Trip Initiated...
Page 50
Table 3-7 Controller Pre-Trip Test Codes (Sheet 2 of 4) Requirements: For units equipped with secondary supply probe only. Pass/Fail Criteria: The temperature difference between primary and secondary probe (supply) is compared. P5-1 Supply Probe Test NOTE If this test fails, “P5-1” and FAIL will be displayed. If both Probe tests (this and the SUPPLY/ RETURN TEST) pass, because of the multiple tests, the display will read ’P 5’...
Page 51
Table 3-7 Temperature Controller Pre-Trip Test Codes (Sheet 3 of 4) Note, this test is skipped if the unit does NOT have: A compressor discharge sensor (CPDS). A discharge pressure transducer (DPT). Condenser pressure transducer (CPT). In addition, this test is skipped if: The sensed ambient temperature is less than 7_C (45_F).
Page 52
Table 3-7 Controller Pre-Trip Test Codes (Sheet 4 of 4) Requirements: Test P8-1 must pass for this test to execute. Setup: The left display will read “P8-2,” and the right display will show the supply air temperature. A 60 minute timer is started. The unit will be required to main- tain the 0°C temperature to within + or -- 0.5_C (0.9_F) of set point until a Data- CORDER recording is executed.
Table 3-8 DataCORDER Function Code Assignments NOTE Inapplicable Functions Display “-- -- -- -- -- ” To Access: Press ALT. MODE key Code TITLE DESCRIPTION Recorder Supply Current reading of the supply recorder sensor. Temperature Recorder Return Current reading of the return recorder sensor. Temperature USDA 1,2,3 Temper- dC3-5...
Table 3-9 DataCORDER Pre-Trip Result Records Test TITLE DATA Heater On Pass/Fail/Skip Result, Change in current for Phase A, B and C Heater Off Pass/Fail/Skip Result, Change in currents for Phase A, B and C Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed, Condenser Fan On Change in currents for Phase A, B and C Condenser Fan Off...
Table 3-10 DataCORDER Alarm Indications To Access: Press ALT. MODE key Code No. TITLE DESCRIPTION The supply recorder sensor reading is outside of the range of --50_C to 70_C (--58_F to +158_F) or, the probe check logic has determined there is a fault with this sensor.
SECTION 4 OPERATION 4.1 INSPECTION (Before Starting) 4.2.2 Connection to190/230 vac Power An autotransformer (Figure 4-1) is required to allow WARNING operation on nominal 230 volt power. It is fitted with a 230 vac cable and a receptacle to accept the standard Beware of unannounced starting of the 460 vac power plug.
clear the gap between the slots, loosen the wing nut until position (100% position). The closed position is 0% air the disc clears the stop. Figure 4-2 gives air exchange flow position.The operator may also adjust the opening values for an empty container. Higher values can be to increase or decrease the air flow volume to meet the expected for a fully loaded container.
4.4.2 Water-Cooled Condenser with Condenser Check and, if required, reset controller Function Codes Fan Switch (Cd27 through Cd39) in accordance with desired operating parameters. Refer to paragraph 3.2.2. a. Connect the water supply line to the inlet side of con- 4.7.3 Start Temperature Recorder denser and the discharge line to the outlet side of the condenser.
three automatic tests (depending on software revision CAUTION installed). These tests will automatically perform a When a failure occurs during automatic series of individual pre--trip tests. The user may also testing the unit will suspend operation scroll down to select any of the individual tests. The awaiting operator intervention.
power to the unit. The heater is connected to a set of In this configuration, a probe check will not be run as a normally closed auxiliary contacts on the compressor part of a normal defrost, but only as a part of a defrost contactor.
FALLING RISING TEMPERATURE TEMPERATURE +1.5 C (2.7 C (1.8 COOLING COOLING +0.5 C (0.9 +.20 SET POINT - -0.20 - -0.5 C (0.9 - - 1 C (1.8 CIRCULATION CIRCULATION ONLY ONLY - - 1.5 C (2.7 Figure 4-4 Controller Operation - - Frozen Mode NOTE ENERGIZED DE- -ENERGIZED...
4.10.2 Sequence Of Operation - - fan motors (ES) energized and the COOL light illumi- Perishable Mode Heating nated. (See Figure 4-7.) b.When the air temperature decreases to a predeter- NOTE mined tolerance above set point, the in-range light is The unit will heat only when in the Perishable illuminated.
Manual Defrost/Interval key operation: When a request for defrost is made by demand defrost , the unit will enter defrost when the reading at the Defrost Depressing and holding the Defrost Interval key for Temperature Sensor is at or below 18°C (64.4°F). five (5) seconds will initiate defrost.
4.11 EMERGENCY OPERATION 4.11.2 Emergency Defrost Operation. Operation by the refrigeration controller may be To place the unit in the emergency defrost mode of overridden by use of the EMERGENCY BYPASS or by operation, cut the wire tie installed at the switch use of the EMERGENCY DEFROST switch.
Page 65
SECTION 5 TROUBLESHOOTING REMEDY/ REFERENCE CONDITION POSSIBLE CAUSE SECTION 5.1 UNIT WILL NOT START OR STARTS THEN STOPS External power source OFF Turn on Start-Stop switch OFF or defective Check No power to unit No power to unit Circuit breaker tripped or OFF Check Autotransformer not connected 4.2.2...
Page 66
REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING Compressor Compressor valves defective Abnormal pressures Controller malfunction Evaporator fan or motor defective 6.16 Refrigeration System Refrigeration System Suction modulation valve malfunction 6.18 Condenser Pressure Transducer defective Check Shortage of refrigerant 6.7.1...
REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.6 UNIT WILL NOT DEFROST PROPERLY - -Continued Frequent defrost Wet load Normal Will not terminate defrost Unit in Emergency Defrost mode 4.11.2 5.7 ABNORMAL PRESSURES (COOLING) Condenser coil dirty 6.10 Condenser fan rotating backwards 6.11 Condenser fan inoperative 6.11...
Page 68
REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.10 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW Frost on coil Evaporator coil blocked Evaporator coil blocked Dirty coil 6.15 Evaporator fan motor internal protector open 6.16 Evaporator fan motor(s) defective 6.16 No or partial evaporator air flow No or partial evaporator air flow Evaporator fan(s) loose or defective 6.16...
(see Figure 6-3) is required for service of the models covered within this manual. The manifold gauge/hose set is available from Carrier Transicold. (Carrier Transicold P/N 07-00294-00, which includes items 1 through 6, Figure 6-3.) To perform service using the manifold gage/hose set, do the following: a.
5. Front seat both manifold gauge set valves and dis- connect from cylinder. The gauge set is now ready for use. To Low Side To High Side Service Port Service Port 7-BLUE 8-YELLOW Blue 9-RED - Red - Yellow 1. Discharge Service 7.
Page 71
After repairs have been made, be sure to perform a volume displacement) and an electronic vacuum refrigerant leak check (refer to paragraph 6.5), and gauge. (The pump is available from Carrier Trans- evacuate and dehydrate the low side (refer to para- icold, P/N 07-00176-11.) graph 6.6).
6.7 REFRIGERANT CHARGE 6.7.1 Checking the Refrigerant Charge NOTE To avoid damage to the earth’s ozone layer, use a refrigerant recovery system whenever remov- ing refrigerant. When working with refrigerants you must comply with all local government envi- ronmental laws. In the U.S.A., refer to EPA sec- tion 608.
Page 73
e. Partially frontseat (turn clockwise) the suction service valve and slowly add charge until the refrigerant appears at the proper level . 6.8 COMPRESSOR WARNING Make sure power to the unit is OFF and power plug disconnected before replacing the compressor. NOTES The compressor should not operate in a vacuum greater than 500 mm/hg (20...
6.8.2 Compressor Disassembly WARNING Before disassembly of any external com- pressor component make sure to relieve possible internal pressure by loosening the bolts and tapping the component with a soft hammer to break the seal. CAUTION Removing the compressor motor press-fit 1.
h. Be very careful not to damage the motor windings Set screw must be removed. when removing motor end cover (see Figure 6-11), as the cover fits over the winding coils. Loosen the cap screws, break the seal and then re- move all capscrews except one in the top of the cover.
difficult to reinstall used valves so that they will seat as before removal. Any valve wear will cause leakage. 1. Equalizer Tube and 3. Counterweight -- Lock Screw Assembly Motor End 2. Lockwasher Figure 6-12 Equalizing Tube and Lock Screw Assembly 1.
Page 77
6.8.6 Compressor Oil Level 6.8.6. d. Removing Oil from the Compressor CAUTION Use only Carrier Transicold approved 1 If the oil level is above one-eighth sight glass, oil must be removed from the compressor. Polyol Ester Oil (POE) - - Castrol-Icematic SW20 compressor oil with R-134a.
6.9 HIGH PRESSURE SWITCH 6.10 CONDENSER COIL The condenser consists of a series of parallel copper 6.9.1 Replacing High Pressure Switch tubes expanded into copper fins. The condenser coil a. Turn unit start-stop switch OFF. Frontseat both suc- must be cleaned with fresh water or steam so the air flow tion and discharge service valves to isolate compres- is not restricted.
Page 79
refrigerant vapor is admitted to the shell side and is c. De-scale water tubes with Oakite No. 32 to remove condensed on the outer surface of the coil. scale. Rust, scale and slime on the water-cooling surfaces d. Flush. inside of the coil interfere with the transfer of heat, e.
6 Allow the Oakite No. 32 solution to soak in the tube coils for several hours, periodically pump-circulating Fill condenser with clean- it with an acid-proof pump. ing solution. Do not add solution more rapidly than vent can exhaust gases An alternate method may be used whereby a pail caused by chemical (see Figure 6-18) filled with the solution and...
1. Automatic control of the refrigerant flow to match the f. From the temperature/pressure chart (Table 6-9), de- evaporator load. termine the saturation temperature corresponding to the evaporator outlet test pressures at the suction 2. Prevention of liquid refrigerant entering the com- modulation valve.
Braze Rod (’Sil-Phos” = 5.5% Silver, 6% Phosphorus) Copper Tube (Apply heat for 10-15 seconds) Bi-metallic Tube Connection Use of a wet cloth is not neces- (Apply heat for 2-5 seconds) sary due to rapid heat dissipation of the bi--metallic connections Figure 6-21 Hermetic Thermostatic Expansion Valve Brazing Procedure 2.
into the indentation of the suction line. See 6.16.1 Replacing The Evaporator Fan Assembly Figure 6-19 for bulb placement. WARNING 4 Check superheat. (Refer to paragraph 6.14.2 step Always turn OFF the unit circuit breakers 6.14.1 ) Container box temperature should be at (CB-1 &...
a. Assemble the motor and plastic spacer onto the sta- WARNING tor. With power OFF discharge the capacitor before disconnecting the circuit wiring. b. Apply loctite to the 1/4-20 x 3/4 long bolts and torque to 0.81 mkg (70 inch-pounds). 6.17.3 Checking The Capacitor c.
Page 85
Checking with SMA-12 portable stepper drive tester eration for a few minutes. While in pulldown the unit The SMA-12 portable stepper drive tester (Carrier will open the SMV to a maximum discharge pressure Transicold P/N 07-00375-00) is a battery operated...
“C” and “D” can be checked as follows: the “ON” position. If the circuit breakers do not hold in, check voltage supply. 1. Install a jumper assembly (Carrier part number 07--00408--00) to connect the drive module and con- c. There is no internal protector for this transformer troller connectors as shown in Figure Figure 6-25.
Figure 6-26 Controller Section of the Control Box 3. After the enter key has been pressed the display will read CAL (for calibration). a. Obtain a grounding wrist strap (Carrier Transicold part number 07--00--304--00)and a static dissipation mat (Carrier Transicold part number 07--00304--00.
Page 88
TP 4 6. The Display will show the message “Pro SoFt.” This message will last for up to one minute. This test point enables the user to check if the internal 7. The Display module will read “Pro donE” when the protector for the condenser fan motor(IP-CM) is open or software loading has loaded.
value for the connectors (MA, MB, MC, KA & KB) is 0.12 (9 inches). Slide the cap and grommet off well mkg (10 inch-pounds). mounted sensor and save for possible reuse. Do not cut the grommet. 6.21.5 Battery Replacement c. If required, prepare the replacement sensor by cut- If required, use tool 07-00418-00.
CAUTION NOTE Do not allow moisture to enter wire splice The P5 Pre-Trip test must be run to inactivate area as this may affect the sensor resis- probe alarms (refer to paragraph 4.8). tance. m. Reinstall sensor, refer to paragraph 6.22.3. REPLACEMENT 2 WIRE TO 2 WIRE OR 3 WIRE TO 3 WIRE BLACK...
Page 91
6.23 ELECTRONIC PARTLOW TEMPERATURE If the optional DataCORDER battery pack is being used, RECORDER and the charge is too low to enable recording during the power off period of less than two days, the pen tip will The microprocessor based temperature recorder is move to below the inner chart ring for the period when no designed to interface with the DataCORDER to log data was recorded by the DataCORDER.
Recorder Door Connector Change Chart Button Calibration Button (Located underneath) Recorder Box Mounting Screws, #10-24 x 7/16 inches long Pen Tip Hold Down Tab Stylus Arm Chart Retaining Nut Figure 6-31. Electronic Partlow Temperature Recorder 6.23.3Adjusting the Recorder Stylus 6.23.4Rezeroing the Recording Thermometer Electronic Partlow Recorder...
Electronic Partlow Recorder The temperature recorder may be fitted with a 12-00464-01: thermistor probe (Simpson accessory #344) attached at the recorder bulb. The thermistor wiring is brought from NOTE the bulb location to a receptacle located in the chart platen of the recorder. If a thermistor is provided, the Use chart CTD P/N 09-00128-00 (°F) recorder chart reading may be checked using a P/N 09-00128-01 (°C).
Page 94
should be stabilized at a temperature of 0°C (32°F). This (clockwise) lowers stylus reading. Then retighten set screw. is accomplished by using one of the two following methods, whichever is more convenient. 3 Reset control at 0°C (32°F), start the refrigeration unit and repeat accuracy check.
Mechanical Temperature Set Screw Recorder Bulb Pinion Shaft Element Recorder Door Recorder Box Stylus 31 Day Clock Clock Winding Key Mechanism and Platen Assembly Push Rod Figure 6-32. Partlow Mechanical Temperature Recorder 6.25 SAGINOMIYA TEMPERATURE RECORDER a. Install new chart on platen. b.
temperature. Rotate the chart by hand. The b. Remove nut and bushing (item 18, Figure 6-33). indicated temperature should be 0°C (32°F). c. Install replacement probe and bushing. Seal with 6.25.3Replacing Sensor Probe silicone before securing to case. a. Remove box from unit. d.
6.27 COMPOSITE CONTROL BOX REPAIRS become stripped, or if the insert becomes loose. The inserts and epoxy are contained in repair kit, Carrier 6.27.1 Introduction Transicold part number 76-50084-00 (see Table 6-4).
Static Mixing Tube (Loctite 983440) 07--00390--00 . . . Instruction Sheet 98--02338--00 Note: Insert repair procedures require use of an Application Gun, Carrier part number 07--00391--00 (Loctite 983435) Table 6-5 Drill Information Item Insert part number Drill size and depth 34- 06231- 01 10.3 mm x 17.8 mm deep (.404 in.
6.28 COMMUNICATIONS INTERFACE MODULE c.. Remove the circuit breaker panel, with circuit INSTALLATION breaker, from the control box. d.. Locate, wires CB21/CIA3, CB22/CIA5 CB23/CIA7 that have been tied back in the wire harness. Remove the protective heat shrink from the ends of the wires. e..
Table 6-7 Wear Limits For Compressors MAXIMUM WEAR MAXIMUM WEAR FACTORY MAXIMUM FACTORY MAXIMUM FACTORY MINIMUM FACTORY MINIMUM BEFORE REPAIR PART NAME PART NAME inches inches inches MAIN BEARING Main Bearing Diameter 1.6268 41.3207 .0020 0.0508 Main Bearing Journal Diameter 1.6233 41.2318 .0020...
Note: Curves to be used as troubleshooting guide only for model series 69NT40 with fresh air makeup vent closed, unit powered on 460 VAC/60hz and SMV 100% open. (Bar) psig (22.0) (20.7) (19.3) (17.9) 35_F (1.7_C) (16.6) (15.2) (13.8) (12.4) (11.0) (9.7) (8.3)
Page 104
(Bar) psig (.97) (.83) (.69) (.55) 35_F (1.7_C) Box (.41) (.28) (.14) 0_F (--17.8_C) Box (- -.14) - -2 (- -.28) - -4 (- -.41) - -6 (48.9) (_C) (15.6) (21.1) (26.7) (32.2) (37.8) (43.3) Ambient Air Temperature Compressor Suction Pressure Versus Ambient Air Temperature at Stable Box Temperature 35_F (1.7_C) Box 0_F (--17.8_C) Box (_C)
Page 105
SECTION 7 ELECTRICAL WIRING SCHEMATIC 7.1 INTRODUCTION This section contains the Electrical Schematics and Wiring Diagrams. The diagrams are presented as follows: Figure 7-1 Provides the legend for use with all figures. Figure 7-2 Provides the schematic diagram for units with normal evaporator fan operation. Figure 7-3 Provides the schematic diagram for units with single evaporator fan capability.
SEE FIGURE SEE FIGURE 7--2 or 7--3 7--2 or 7--3 TO DL, TERMINAL C SEE SEE FIGURE 7--2 or 7--3 TransFRESH CONTROLLER VENT POSITION SENSOR Note: DPT may not be installed if unit is equipped with VPS SEE FIGURE 7--2 or 7--3 SEE FIGURE 7--2 or 7--3 SEE FIGURE...
4 Heaters 6 Heaters T11 T4 T3 T2 T1 P2 P1 T11 T4 T3 T2 T1 P2 P1 [DF11] ECD3 COMBINATION [ED5] SINGLE SENSOR J G F E D C J G F E D C SENSOR CONFIGURATION ECE3 [ED8] TRC1 TRC2 WIRES TO TR X2...
Page 111
FOR UNITS WITHOUT ELECTRONIC CR ONLY, FOR CR WIRING, SEE FIGURE 7- -7 (COMBINATION SENSOR ONLY) [ED6] [ED9] NOTE: RM MAY BE OUTSIDE BOX SDDC [BMDC] SDON [BMON] HPRB SDGD [BMGD] [ED3] CFA1 SDS1 [CFS2] [BMS1] SDS2 [BMS2] SINGLE SENSOR ONLY (UNITS WITHOUT ED ONLY) [ED12]...
6 HEATERS 4 HEATERS T11 T4 T3 T2 T1 P2 P1 T11 T4 T3 T2 T1 P2 P1 [DF11] ECD3 COMBINATION SINGLE SENSOR [ED5] J G F E D C J G F E D C SENSOR CONFIGURATION ECE3 [ED8] TRC2 TRC1 EM2A...
Page 113
FOR UNITS WITHOUT ELECTRONIC CR ONLY, FOR CR WIRING, SEE FIGURE 7- -7 (COMBINATION SENSOR ONLY) E1A2 [ED6] (WHT) [ED9] NOTE: RM MAY BE OUTSIDE BOX SDDC [BMDC] SDON [BMON] SDGD [BMGD] [ED3] DPTB DPTC CFA1 SDS1 [CFS2] [BMS1] S1L4 E1F4 SDS2 [BMS2]...
[DF11] ECD3 [ED5] SINGLE SENSOR COMBINATION ECE3 CONFIGURATION SENSOR [ED8] TRC2 TRC1 WIRES TO TR X2 EDL, DF--(TFC), P--(TFC), CIB1, GRD, CHA2, RMA, KA12, EFA2, HRA2, CR8, HPRB, HRA2,HPT5 & DHH (SEE Figure 7-9) (ICF MAY BE IN CONTROL BOX) NOTE: WHEN EB, ED, BM OR CFS IS/ARE INSTALLED, WIRE DESTINATIONS CHANGE FROM THE STANDARD.
Page 115
FOR UNITS WITHOUT ELECTRONIC CR ONLY, FOR CR WIRING, SEE FIGURE 7- -7 (COMBINATION SENSOR ONLY) [ED6] [ED9] NOTE: RM MAY BE OUTSIDE BOX SDDC [BMDC] SDON [BMON] HPRB SDGD [BMGD] [ED3] DPTB [VPS2] [VPS1] DPTC [VPS3] CFA1 SDS1 [CFS2] [BMS1] SDS2 [BMS2]...
FROM TRX1 SEE Figure 7-6 SHEET 1 NOTE: STANDARD CONTROLLER JUMPERS: MA3 TO MA7 AND MA9 TO MA11 (SEE Figure 7-2 SHEET 1) ARE REMOVED IN THIS APPLICATION Figure 7-9 WIRING DIAGRAM - - Electronic Partlow Temperature Recorder T-285 7-14...
Page 120
INDEX Safety and Protective Devices, 2-9 Manifold Gauge Set, 6-1 Sampling Type, 3-10 Microporcessor System, 3-1 Sensor Configuration, 3-8 Modes Of Operation, 3-3 Sequence Of operation, 4-6 Motor Current, 6-35 Service Valves, 6-1 Starting, 4-3 Stopping, 4-3 Suction Modulating Valve, 6-16 Oil Level , 6-9 Operational Software, 3-3, 3-7 Temperature Control, 3-4, 3-5...
Page 121
Carrier Transicold Division, Carrier Corporation Container Products Group P.O. Box 4805 Syracuse, N.Y. 13221 U.S A www.carrier.transicold.com A member of the United Technologies Corporation family. Stock symbol UTX ã2004 Carrier Corporation D Printed in U. S. A. 03/04...