Alarm
Steps
NO.
227
SERVICE SOON-PM #2 DUE
TRIGGER–ON: The Maintenance Hour Meter #2 time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
2
Perform Maintenance
Perform appropriate engine & unit
maintenance.
3
Reset Maintenance Hour Meter #2
a. Check that Maintenance Hour
Meter #2 interval is set for your
requirements.
b. Reset Maintenance Hour Meter #2
for the next service interval.
228
SERVICE SOON-PM #3 DUE
TRIGGER–ON: The Maintenance Hour Meter #3 time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
2
Perform Maintenance
Perform appropriate engine & unit
maintenance.
3
Reset Maintenance Hour Meter #3
a. Check that Maintenance Hour
Meter #3 interval is set for your
requirements.
b. Reset Maintenance Hour Meter #3
for the next service interval.
62-11389
Alarm/Cause
7−100
Corrective Action
Must be done soon!
Follow instructions on proper maintenance form.
Reset configured Interval if required.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.
Must be done soon!
Follow instructions on proper maintenance form.
Reset configured Interval if required.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.