Carrier VECTOR 6500 Operation & Service Manual page 120

Single-temp trailer and rail refrigeration units with advancet microprocessor
Table of Contents

Advertisement

SS PRODUCTSHIELD ECONO
MIN TEMP
SS PRODUCTSHIELD ECONO
MAX TEMP
SS PRODUCTSHIELD
ECONO - DELTA-T
(used for "Go To S/S" only, not
available for "Go To Cont")
S PRODUCTSHIELD HIGH AIR
SS HIGH AIR MIN. TEMP
SS HIGH AIR MAX. TEMP
SS HIGH AIR DELTA-T
S PRODUCTSHIELD WINTER - XX° OFF
62-11389
Table 5−2 Microprocessor Configurations - Continued
OFF or
-20°F to +119.0°F
(-28.9°C to
+48.4°C )
(in 0.5° incre-
ments)
Default: 119.0°F
(48.4°C )
OFF or
-20°F to +119.0°F
(-28.9°C to
+48.4°C )
(in 0.5° incre-
ments)
Default: 119.0°F
(48.4°C)
OFF
+3.6°F to +27.0°F
(+2°C to 15°C) (in
0.5° increments
OFF
ON
OFF
-19°F to +119°F
(-28.3°C to
+48.3°C )
in 0.5°F or °C
increments
Default: 119°F
(48.3°C )
OFF
-19°F to +119°F
(-28.3°C to
+48.3°C )
in 0.5°F or °C
increments
Default: 119°F
(48.3°C )
OFF
+3.6° F to +27.0°F
(+2°C to 15°C)
in 0.5° C or °F in-
crements
-20°F to +32.0°F
(-28.9°C to 0°C) (in
0.5° C or °F incre-
ments
OFF = There is no lower limit for this parameter.
Select the lowest ambient temperature desired to
activate ProductShield Econo.
If ProductShield Econo is Go To Continuous there
is a minimum 10°F range. Therefore, this parame-
ter's upper limit is ProductShield Econo Maximum
Temperature minus 10°F (5.5°C).
OFF = There is no upper limit for this parameter.
Select the highest ambient temperature desired to
activate ProductShield Econo
If ProductShield Econo Install is Go To Continuous
there is a minimum 10°F range. Therefore, this pa-
rameter's lower limit is ProductShield Econo Min
Temp plus 10°F (5.5°C).
OFF = Delta-T is not used in determining when the
unit will go into Econo: Go To Start/Stop mode.
Select the desired delta-T value for activation of
ProductShield Econo. When Delta-T is below this
setting and within the minimum/maximum range, go
to start/stop will be allowed
OFF = The unit will operate normally in high and
low speeds.
ON = The unit will operate in high speed when the
ambient air temperature is outside a user defined
range. This provides increased air flow and good
product protection for extreme ambient temperat-
ures. Unit may return to low speed when ambient
comes back within the range.
OFF = There is no lower limit for this parameter.
Select the lower limit of the ambient range desired
for this parameter. Refer to Section 4.7.3 for more
information on High Air Min. Temp.
OFF = There is no upper limit for this parameter.
Select the upper limit of the ambient range desired
for this parameter. Refer to Section 4.7.3 for more
information on High Air Max. Temp.
OFF = Delta-T is not used for determining the activ-
ation/de-activation of High Air Delta-T
Select the desired Delta-T value for activation of
ProductShield High Air. Refer to Section 4.7.3 for
more information on High Air Delta-T.
Select the desired ambient temperature below
which ProductShield Winter will operate (forced
Continuous Run operation.)
5−18