Carrier VECTOR 6500 Operation & Service Manual page 176

Single-temp trailer and rail refrigeration units with advancet microprocessor
Table of Contents

Advertisement

Alarm
Steps
NO.
59
DATALOGGER (DataLink data recorder) NOT RECORDING
TRIGGER–ON: No data is being recorded by the DataLink data recorder.
UNIT CONTROL: Engine and Standby Operation: alarm only.
RESET CONDITION: Alarm may be manually reset via keypad.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 page 7−2.) Operate the unit through the appropriate modes to see if any active alarm
occurs. Continue with the steps below as necessary.
1
Clear Alarm
a. Clear Active Alarm(s).
b. Check
re-occurrence.
2
Microprocessor Defective
a. Download previous data using
Download
ReeferManager Program.
b. Replace microprocessor & set
Configurations,
Parameters,
removed
Maintenance
DataLink data recorder Setup.
NOTE: Specific configurations may be found on the TransCentral Website (Authorized Carrier Transicold
Dealers only.)
Alarm/Cause
for
Active
Alarm
PC
Card,
or
Functional
Enter
hours
from
microprocessor,
set
Hour
Meters,
and
7−43
Corrective Action
Alarms Clear.
If Inactive, download all data & retain.
If Active, go to next step.
Data retrieval OK.
New microprocessor in place.
62-11389