Service Mode; Pc Mode; Table 5−1 Component Test - Carrier VECTOR 6500 Operation & Service Manual

Single-temp trailer and rail refrigeration units with advancet microprocessor
Table of Contents

Advertisement

Component / Menu List
Green Light
Amber Light
Defrost Light
Front Unloader (UL1)
Rear Unloader (UL2)
Speed Relay (SR)
Buzzer (B)
Glow Plug (Intake Air Heater) Relay (GP or
IAHR)
Heater Contactor 1 (1HTCON1)
Heater Contactor 2 (1HTCON2)
Evaporator Motor Contactor (1EVCON)
Power Supply Contactor Relay (PSCONR)
Compressor Motor Contactor Relay (CCONR)
Condenser Motor Contactor (CDCON)
Generator Contactor Relay (GENCONR)
Main Menu ( Press the "=" key to go back to the the Configuration Mode or Service Mode
selection menu. Press the down or up arrow to continue scrolling the component test list.)

5.2.3 Service Mode

CAUTION
Service Mode MUST be used whenever re-
moving refrigerant charge, refrigerant leak
checking or evacuating.
NOTE
If the Main Power switch is toggled to the OFF
position, the microprocessor will exit service
Mode.
To enter Service Mode:
a. Enter the Technician Interface - Service Mode as de-
scribed in Section 5.2.
b. "ENTERING SERVICE MODE" will display in the
MessageCenter.
When entering Service Mode the microprocessor opens
the CSMV and EXV to 100% open.
c. Once the valves are open, "RECOVER / LEAK CHK /
EVAC MODE" is displayed in the MessageCenter.
d. Refrigerant recovery, leak checking, or evacuation
may be performed on the unit at this time. Refer to
Service Procedures in Section 8.
e. The unit should remain in the RECOVER / LEAK CHK
/ EVAC MODE as these service procedures are per-
Table 5−1 Component Test
MessageCenter
LIGHT OFF IN X MINS
LIGHT OFF IN X MINS
LIGHT OFF X MINS
UL1 OFF IN X MINS
UL2 OFF IN X MINS
SR OFF IN X MINS
BUZZER OFF IN X MINS
RELAY OFF IN X MINS
HEATER CONT 1 OFF IN 5 MINS
HEATER CONT 2 OFF IN 5 MINS
EVAPORATOR CONT 1 OFF IN 5 MIN
POWER SUPPLY CONT OFF IN X MIN
COMPRESSOR CONT OFF IN X MINS
CONDENSER CONT OFF IN X MINS
GENERATOR CONT OFF IN 5 MINS
formed. If the unit shifts to Charge Mode and
"CHARGE MODE – HOLD = TO EXIT" is displayed in
the MessageCenter, DO NOT perform refrigerant re-
covery, leak checking, or evacuation. Exit Service
Mode and then re-enter, making sure that "RE-
COVER / LEAK CHK / EVAC MODE" is displayed in
the MessageCenter before continuing any of these
service procedures.
f. The microprocessor will monitor the pressure trans-
ducer readings during evacuation. Once all pressure
transducers (CDP, CSP and EVOP) have dropped
below –20 inhg (0.68 Bar) and then 2 of the 3 pressure
transducers rise above 5 PSIG (0.34 Bar ), the micro-
processor will close CSMV and EXV to 0% open.
When the valves are closed, "CHARGE MODE –
HOLD = TO EXIT" is displayed in the Mes-
sageCenter. This action is taken to prevent refriger-
ant migration to the compressor during charging,
g. To exit Service Mode at any time, press and hold the
"=" key for 3 seconds. "EXITING SERVICE MODE"
will then display in the MessageCenter.

5.3 PC MODE

PC Mode allows the technician to access the
microprocessor without the engine running and without
the refrigeration system running. When in PC Mode the
microprocessor is fully functional and all Operator
Interfaces may be performed, the operation of the
microprocessor may be demonstrated and all PC
functions may be performed, again, without the unit
actually operating.
5−3
FET
Board
LED
7 & 14
14
16
23
22
27
18
30
10
21
20
19
2
1
3
62-11389