Parameters Setable in Quick Programming Mode
The minimum parameters required for Inverter operation can be monitored and set in quick programming
mode. The parameters displayed in quick programming mode are listed in the following table. These and all
other parameters, are also displayed in advanced programming mode.
Refer to the overview of modes on page 3-5 for an overview of quick programming mode.
Param-
eter
Number
b1-01
b1-02
b1-03
C1-01
C1-02
C6-02
-4
5
Name
Description
LCD Display
Reference
Set the frequency reference input
selection
method.
0: Digital Operator
1: Control circuit terminal (analog
input)
2: RS-422A/485 communications
Reference
3: Option Card
Source
Operation
method selec-
Set the run command input method
tion
0: Digital Operator
1: Control circuit terminal (sequence
input)
2: RS-422A/485 communications
3: Option Card
Run Source
Select stopping method when stop
command is input.
0: Ramp to stop
Stopping
method selec-
1: Coast to stop
tion
2: DC braking stop (Stops faster than
coast to stop, without regenerative
operation.)
3: Coast to stop with timer (Run com-
mands are disregarded during
Stopping
Method
deceleration time.)
Acceleration
Set the acceleration time in seconds
time 1
for the output frequency to climb from
Accel Time 1
0% to 100%.
Deceleration
Set the deceleration time in seconds
time 1
for the output frequency to fall from
100% to 0%.
Decel Time 1
Carrier fre-
quency selec-
tion
Select carrier wave fixed pattern.
Select F to enable detailed settings
using parameters C6-03 to C6-07.
Carrier-
FreqSel
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to 3
1
No
Q
0 to 3
1
No
Q
0 to 3
0
No
Q
Yes
Q
0.0 to 6000.0
10.0 s
Yes
Q
1 to F
6
No
Q
RS-422A/
485 Reg-
ister
180H
181H
182H
200H
201H
224H