Section 5 Functions and Operations

5.32 Copying Bank Comparative Set Values

4
copy
L
(COPY)
0
L
Displays "L 0."
sv. bnk
4
L
0
Displays "L 4."
sv. bnk
4
L
0
sv. bnk
4
L
1
sv1. hh
4
L
10000
copy
4
L
off
copy
4
L
off
copy
4
L
on
sv. bnk
4
L
1
5-82
The bank copy function is used to specify a bank between 0 and 7 and
copy the group of comparative set values in that bank to all banks.
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least 3 s in RUN level to move to
L
the initial setting level.
3 s min.
0" is displayed on the level/bank display to indicate the initial
• "
L
setting level.
B Press the L [LEVEL] Key several times to move to the comparative
L
set value level.
4" is displayed on the level/bank display to indicate the
• "
L
comparative set value level.
C Press the S [SHIFT] Key to make the SV display flash.
S
• The setting can be changed when the SV display starts to
flash.
D Use the U [UP] Key to select the bank to be copied from.
U
E Press the M [MODE] Key to switch to the next parameter.
M
• Change the comparative set values HH, H, L, and LL as
required.
F Press the M [MODE] Key several times to change the PV display
M
to "copy."
G Press the S [SHIFT] Key to make the SV display flash.
S
• The setting can be changed when the SV display starts to
flash.
H Use the U [UP] Key to change the SV display to "on."
U
I Press the M [MODE] Key to switch to the next parameter.
M
• The comparative set value from the copy source bank selected
in step D will be copied to all banks.
Comparative set value
R
P C