Omron K3HB-C User Manual page 38

Digital indicators
Hide thumbs Also See for K3HB-C:
Table of Contents

Advertisement

■ Settings for the K3HB-R
RUN Level
Initial Setting Level (
Input Adjustment Level
1)
(
L
Display Adjustment Level
2)
(
L
Parameter
Characters
Comparative
set value HH
Comparative
set value H
Comparative
set value L
Comparative
set value LL
✽ Check on the status displays.
0)
L
Parameter
Function
Input type A
Prescale AX
Prescale AY
Decimal point
position
Comparative
output pattern
Parameter
Averaging type
Averaging
times
Auto-zero time
A
Parameter
Display value
selection
Position meter
type
Position meter
upper limit
Position meter
lower limit
3.1 Monitoring Roller Speed: K3HB-R
Set
value
3400
Control example for the following
3200
settings:
HH alarm: 3,400 rpm
H alarm: 3,200 rpm
800
L alarm: 800 rpm
LL alarm: 400 rpm
400
Characters Set value
func
f1
Rpm/circumferential
speed
in-ta
00
No-contact (NO)
ps. ax
0. 1250
ps. ay
10 00
Prescale value ( ) = 1/8 =
0.125 = 0.125
dp
,,,,,
No decimal point
out-p
nomal
Standard outputs
Characters Set value
avg-t
smpl
avg-n
1
at. za
10. 0
Characters Set value
disp
pv
pos-t
inc
pos-h
3400
pos-l
400
Remarks
Remarks
0
10
Remarks
Simple averaging
Once
Display is forced to zero
when no pulse is
received for 10 seconds.
Remarks
Present value
Incremental display
Full-scale
400 to 3,400 mm
3-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

K3hb-pK3hb-r

Table of Contents