Setting The Function For The K3Hb-C - Omron K3HB-C User Manual

Digital indicators
Hide thumbs Also See for K3HB-C:
Table of Contents

Advertisement

5.3 Setting the Function for the K3HB-C

■ F1: Individual Inputs
The count in incremented on input A pulses and decremented on input
B pulses.
The count is incremented on the rising edge of input A and
decremented on the rising edge of input B. When both inputs A and B
turn ON at the same time, the count does not change.
The measurement value can be obtained using the following formula:
D = C
C: Count
: Prescale value A or prescale value B
D: Measurement value
Note: If F1 (individual inputs) is used, both preset value A and preset
value B must be set.
Input A
Input B
HOLD
1
Count
0
Holding the Measurement Value
Turning ON the HOLD input temporarily stops the cumulative count
and holds the measurement value. The outputs are also held.
Resetting the Display Value
The display value can be zeroed by turning ON the RESET input or
press the MAX/MIN Key for 1 second or longer.
While the RESET input is ON, measurement is not performed, the
display shows "-----", and all outputs are OFF.
Compensation Value Input
Use the compensation input to start measurement from the desired
value. The compensation value must be set in advance.