Section 5 Functions and Operations

5.12 Outputting for a Set Interval

f
shot
L
(SHOT)
5-44
The shot output function turns OFF a comparative output after a set
interval after it turns ON. The following diagram shows operation when
the shot output is set to 100 ms on the K3HB-R.
Comparative
set value H
Measurement value
Comparative
set value L
Output H
Output L
The shot output time is set using the following parameter.
Parameter
Shot output
shot
* The unit for K3HB-R settings is 100 ms. For example, if 10 is set,
then the shot output time is 10
The shot output time is an internal calculation time. The following times
are added to the set time to give the actual output time.
• For relay outputs: 11 ms max.
• For transistor outputs: 1 ms max.
Advanced function setting level
100 ms
100 ms
Set value
Meaning of set value
0 to 1999
0 to 1,999 ms (0 to 199.9 s)*
The shot output will be
disabled when set to 0.
100 ms = 1 s.