Omron K3HB-C User Manual page 104

Digital indicators
Hide thumbs Also See for K3HB-C:
Table of Contents

Advertisement

f
hys
L
(HYS)
L
0
L
3 s min.
Displays "L 0."
M
amov
0
L
0
S
amov
0
L
00000
U
init
f
L
off
Displays "L f."
M
M
hys
f
L
1
S
hys
f
L
0001
U
hys
f
L
0050
M
off-d
f
L
0
L
0
L
1 s min.
L
123. 4
123. 4
1 s min.
Hysteresis is set using the following parameter.
Parameter
Hysteresis
hys
* The decimal point depends on the "decimal point position" setting.
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least 3 s in RUN level to move to
the initial setting level.
0" is displayed on the level/bank display to indicate the initial
• "
L
setting level.
B Press the M [MODE] Key several times to change the PV display
to "amov."
• This parameter is not displayed for the initial status due to setting
level protect.
Refer to "5.34 Limiting Key Operations" (P.5-84) for information
on removing setting level protect.
C Press the S [SHIFT] Key to make the SV display flash.
• The setting can be changed when the SV display starts to
flash.
D Use the U [UP] and S [SHIFT] Keys to set the password "-
0169." Press the M [MODE] Key to move to the advanced
function setting level.
f" is displayed on the level/bank display to indicate the
• "
L
advanced function setting level.
E Press the M [MODE] Key several times to change the PV display
to "hys."
F Press the S [SHIFT] Key to make the SV display flash.
• The setting can be changed when the SV display starts to
flash.
G Use the U [UP] and S [SHIFT] Keys to change the set value.
H Press the M [MODE] Key to switch to the next parameter.
• The set value is registered.
I Press the L [LEVEL] Key for at least 1 s to return to the initial
setting level.
J Press the L [LEVEL] Key for at least 1 s to return to RUN level.
5.11 Preventing Output Chattering
Set value
Meaning of set value
0 to 9999
0 to 9,999 *
5-43