Calibrating Voltage Input - Omron E5AK User Manual

Digital controller
Hide thumbs Also See for E5AK:
Table of Contents

Advertisement

CHAPTER 7 CALIBRATION

7.5 Calibrating Voltage Input

F Preparation
F Calibration:
0 to 5 V, 1 to 5 V
Cont'd on next page
7--10
~
AC100-240V
(AC/DC24V
)
10
SOURCE
9
8
7
6
5
4
3
2
1
• In the above figure, STV refers to a standard DC current/voltage
source, and DMM refers to a precision digital multimeter. However,
note that the DMM is required only when the transfer output func-
tion is supported.
This example describes how to calibrate voltage input when the trans-
fer output function is supported. If the transfer output function is not
supported, skips steps (4) to (7).
(1) When [
] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the
key. The display changes to [
display). Set the STV output to 5V . When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(3) Press the
key. The display changes to [
display). Set the STV output to 0V . When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (8). Press the
display changes to [
(5) Set the output to 20mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "20mA".
(6) Press the
key. The display changes to [
display).
(7) Set the output to 4mA by the
voltage on the digital multimeter. In the example on the left, the
display indicates that the value two digits smaller than before cal-
ibration is "4mA".
30
20
31 32
29
19
28
18
27
17
26
16
25
15
24
14
23
13
22
12
33
21
11
DMM
] (20mA calibration display).
or
keys while monitoring
or
keys while monitoring the
+
--
STV
] (5 V calibration
] (0V calibration
key. The
] (4mA calibration

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents