PLCs with More Than One Network Communications Unit
If the relay PLC has more than one Network Communications Unit (see note 1), it is
normally necessary to create and transfer a local network table (see note 2).
Select Tools
Start Routing Table to start the Routing Table Component, set the local
network table, and download it to the relay PLC.
Note 1: In this context, the following are Network Communications Units: Ethernet Unit, Con-
troller Link Unit, SYSMAC LINK Unit, DeviceNet Unit, FL-net Unit, EtherNet/IP Unit, or
built-in EtherNet/IP port: If serial ports are registered in the local network table to treat
them as networks, the serial ports must be treated as Network Communications Units,
including the serial ports on the CPU Unit. An EtherNet/IP Unit, built-in EtherNet/IP
port, or Ethernet Unit can be used.
Note 2: The local network table is one of the routing tables. It lists the unit numbers and net-
work addresses of the network Communications Units.
Number of Network Communications
Overall Procedure
Start the CX-Integrator.
Connect online to the relay PLC.
Create the local network table.
Transfer the local network table to the relay PLC
via the serial connection.
Connect to a Communications Unit/port to
enable accessing it.
Upload the network structure.
Network Configuration Example
Computer running CX-Integrator
Direct serial or
network connection
More Than One Network Communications Unit
(Ethernet Unit, Controller Link Unit, SYSMAC LINK
Unit, DeviceNet Unit, FL-net Unit, EtherNet/IP Unit,
built-in EtherNet/IP port, or Serial Communications
Board/Unit (when the serial port is treated as a
Network Communications Unit))
Local network table registration
Units
Only 1
More than 1
Example: Select Component
from the menu bar to automatically connect
online using a serial connection.
Select Tools - Start Routing Table from the
menu bar.
Create the local network table and select
Option
Right-click the desired network in the Online
Connection Information Window and select
Connect from the pop-up menu.
Right-click and select Transfer [Network to
PC].
Relay PLC (= target PLC)
CS/CJ-series PLC
2-1
Basic Procedures
Not required
Required
Auto Online
Transfer to PLC.
At least one network address must be
assigned in the local network table.
The local network table must be transferred
when the relay PLC is still the target PLC to
register the correspondence between unit
numbers and network addresses.
Required
2-3