Non-Fatal Errors - Omron CP1L CPU UNIT - 06-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

Troubleshooting
9-2-5

Non-fatal Errors

Errors Created with for FAL Instructions
Flash Memory Errors
484
A non-fatal error has occurred if both the RUN indicator and the ERR/ALM
indicator are lit during operation (i.e., in RUN or MONITOR mode).
■ CPU Unit Indicators
POWER
RUN
ERR/AL
INH
PRPHL
BKUP
Information on the non-fatal error can be obtained from the error code on the
7-segment display and from the Error Tab Page of the CX-Programmer's PLC
Error Window. Take corrective actions after checking error details using the
display messages and the Auxiliary Area Error Flags and error information.
• Errors are listed in the following table in order, with the most serious ones
first.
• If two or more errors occur at the same time, the most serious error code
will be stored in A400.
A FAL instruction was executed in the program to create a non-fatal error.
Probable cause
The executed FAL number 001 to 511 will
be stored in A360 to A391. The number 4
will be added to the front of 101 to 2FF
(which correspond to executed FAL num-
bers 001 to 511) and the result will be
stored in A400 as error code 4101 to
42FF.
■ Reference Information
Error flag
FAL Error Flag, A402.15
Error code (A400)
4101 to 42FF
Error information
None
Probable cause
A315.15 will turn ON when writing to the
internal flash memory fails.
■ Reference Information
Error flag
Flash Memory Error Flag, A315.15
Other non-fatal flags, A402.00
Error code (A400)
None
Error information
None
POWER
Lit
RUN
Lit
ERR/ALM
Flashing
INH
---
BKUP
---
PRPHL
---
Possible remedy
Check the conditions for executing FAL
instructions and remove any causes of
the user-defined error.
Possible remedy
Replace the CPU Unit when the internal
flash memory has been written to more
than 100,000 times.
Section 9-2

Advertisement

Table of Contents
loading

Table of Contents