6-1-10 Non-fatal Errors

A non-fatal error has occurred if both the RUN indicator is lit and the ERR/ALM indicator is flashing
during operation (i.e., in RUN or MONITOR mode).
CPU Unit Indicators
POWER
RUN
ERR/AL
INH
PRPHL
BKUP
Information on the non-fatal error can be obtained from the Error Tab Page of the CX-Programmer's
PLC Error Window.
Take corrective actions after checking error details using the display messages and the Auxiliary
Area Error Flags and error information.
• Errors are listed in order with the most serious errors first.
• If two or more errors occur at the same time, the most serious error code will be stored in A400.
Errors Created with FAL Instructions
A FAL instruction was executed in the program to
create a non-fatal error.
(The executed FAL number 001 to 511 will be stored
in A360 to A391. The number 4 will be added to the
front of 101 to 2FF (which correspond to executed
FAL numbers 001 to 511) and the result will be
stored in A400 as error code 4101 to 42FF. )
Reference
Error flag
Error code (A400)
Error information
Backup Memory Error
Writing to the backup memory (built-in EEPROM)
fails. (A315.15 will turn ON. )
CP1E CPU Unit Hardware User's Manual(W479)
: Not lit
: Flashing
: Lit
POWER
RUN
ERR/ALM
INH
PRPHL
BKUP
—: Irrelevant
Cause
FAL Error Flag, A402.15
4101 to 42FF
Cause
Remedy
Check the conditions for executing FAL instructions and
remove any causes of the user-defined error.
Remedy
Replace the CPU Unit when the backup memory (built-in
EEPROM) has been written to more than 100,000 times.