Troubleshooting
Interrupt Task Errors
PLC Setup Errors
Option Board Errors
Battery Error
Probable cause
An interrupt task error occurs when the
Detect Interrupt task errors setting in the
PLC Setup is set to Detect and an attempt
is made to refresh a Special I/O Unit from
an interrupt task with IORF(097) while the
Unit's I/O is being refreshed by cyclic
refreshing (duplicate refreshing).
■ Reference Information
Error flag
Interrupt Task Error Flag, A402.13
Error code (A400)
008B
Error information
Interrupt Task Error, A426
Probable cause
A set value error occurred in the PLC
Setup.
The address of the error is stored in A406
in 16-bit binary.
■ Reference Information
Error flag
PLC Setup Error Flag, A402.10
Error code (A400)
009B
Error information
PLC Setup error location, A406
Probable cause
A315.13 will turn ON if the Option Board
is removed while the power is being sup-
plied.
■ Reference Information
Error flags
Option Board Error Flag, A315.13
Other Non-fatal Error Flag, A402.00
Error code (A400)
---
Error information
---
Probable cause
If the PLC Setup is set to detect battery
errors, this error will occur when there is
an error in the battery in the CPU Unit
(i.e., the voltage is low or a battery is not
mounted).
■ Reference Information
Error flag
Battery Error Flag, A402.04
Error code (A400) 00F7
Error information
---
Possible remedy
Review the program to see whether detect-
ing interrupt task errors can be disabled or
avoided.
Possible remedy
Correct the PLC Setup with correct val-
ues.
Possible remedy
Turn OFF the power supply and then
install the Option Board again.
Possible remedy
Check the battery connections.
When using battery-free operation, dis-
able connecting battery errors in the PLC
Setup.