Analog Output Units - Omron CP1L CPU UNIT - 06-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

Analog Output Units

Ladder Program Example
Operation start 1 cycle ON
A200.11
Always ON
P_On
T5
T5
T5
T5
7-3
Analog Output Units
408
• Expansion Unit errors are output to bits 0 to 6 of word A436. The bits are
allocated from A436.00 in order starting with the Unit nearest the CPU
Unit. Use these flags in the program when it is necessary to detect errors.
Analog
Input range Range code
input
Input 1
0 to 10 V
Input 2
4 to 20 mA
Input 3
-10 to +10 V 00
Input 4
Not used.
MOV(021)
#80EB
102
MOV(021)
#8008
103
TIM5
#0002
Execution
condition
CMP(020)
003
#8000
P_EQ
110.00
Execution
condition
MOV(021)
002
D100
Execution
condition
MOV(021)
003
D101
Execution
condition
MOV(021)
004
D102
Each CP1W-DA041/CPM1A-DA041 Analog Output Unit provides four analog
outputs.
• The analog output signal ranges are 1 to 5 V, 0 to 10 V, -10 to +10 V, 0 to
20 mA, and 4 to 20 mA. The resolution is 1/6,000. The open-circuit detec-
tion function is activated in the ranges of 1 to 5 V and 4 to 20 mA.
• The Analog Input Unit uses four output words, so a maximum of three
Units can be connected.
Averaging
01
Yes
10
Yes
No
-(00)
---
←Writes set data E and B.
←Writes set data 0 and 8.
Input 2 open circuit alarm
←Reads analog input 1 converted value.
←Reads analog input 2 converted value.
←Reads analog input 3 converted value.
Section 7-3
Set data
Destination
word
1101 (B hex) n+1
1110 (E hex) n+1
1000 (8 hex) n+2
0000 (0 hex) n+2

Advertisement