Restrictions On System Configuration - Omron CP1L CPU UNIT - 06-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

System Configuration
Name and
appearance
DeviceNet I/O
Link Unit
CompoBus/S
I/O Link Unit
S
No.
COMM
ERR
BD H
BD L NC(BS-)
1-2-3

Restrictions on System Configuration

Model
CPM1A-DRT21
CP1W-SRT21
CPM1A-SRT21
SRT21
EXP
NC(BS+)
NC
The following restrictions apply to the CP-series Expansion Units and CP-
series Expansion I/O Units that can be connected to CP1L CPU Units.
Number of Expansion Units and Expansion I/O Units Connected
A maximum of three Units can be connected to a CPU Unit with 30 or 40 I/O
points and one Unit can be connected to a CPU Unit with 20 or 14 I/O points.
Mounting Restriction
When connecting CP-series or CPM1A-series Expansion Units or Expansion
I/O Units to a CPU Unit with AC power, provide a space of approximately 10
mm between the CPU Unit and the first Expansion Unit or Expansion I/O Unit.
CP1L CPU Unit
If sufficient space cannot be provided between the CPU Unit and the first
Expansion Unit or Expansion I/O Unit, use the PLC in an ambient temperature
of 0 to 50 ° C.
Restrictions in the External Power Supply Capacity
The following restrictions apply when using the external power supply from a
CPU Unit with AC power.
CPU Units with 30 or 40 I/O Points and AC Power (CP1L-M@@DR-A)
When CP1W or CPM1A Expansion Units or Expansion I/O Units are con-
nected to a CPU Unit with 30 or 40 I/O Points and AC Power (CP1L-M@@DR-
A), it may not be possible to use the entire 300 mA from the external power
supply due to restrictions in the power supply capacity. The entire 300 mA
from the external power supply can be used if Expansion Units and Expansion
I/O Units are not connected.
Specifications
As a DeviceNet Slave, 32 inputs and 32 out-
puts are allocated.
As a CompoBus/S slave, 8 inputs and 8 out-
puts are allocated.
Expansion I/O Units or Expansion Units
10 mm
Section 1-2
Weight
200 g max.
200 g max.
17

Advertisement