Wiring Safety And Noise Controls - Omron CP1L CPU UNIT - 06-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

Wiring CP1L CPU Units
3-4-3

Wiring Safety and Noise Controls

I/O Signal Wiring
Inductive Loads
Note
Example Method 1
OUT
SYSMAC CP1L
R
COM
Use a dark current of approximately 1/3 the rated current of the incandescent lamp.
Example Method 2
OUT
SYSMAC CP1L
COM
Install a limit resistance.
Whenever possible, place I/O signal lines and power lines in separate ducts or
conduits both inside and outside of the control panel.
(1)
(2)
Suspended duct
If the I/O wiring and power wiring must be routed in the same duct, use
shielded cables and connect the shields to the GR terminal to reduce noise.
When an inductive load is connected to an I/O Unit, connect a surge suppres-
sor or diode in parallel with the load as shown below.
IN
Diode
DC input
L
COM
Use surge suppressors and diodes with the following specifications.
L
+
R
L
+
(1)
(2)
In-floor duct
OUT
Relay output
COM
OUT
Relay output or
transistor output
COM
Section 3-4
(1) = I/O cables
(2) = Power cables
(1)
(2)
Conduits
L
Surge suppressor
+
Diode
105