Connection Methods - Omron CP1L CPU UNIT - 06-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

Connections to Serial Communications Option Boards

Connection Methods

Communications Modes and Ports
The following table shows the relationship between the communications ports and the communications modes
for the Serial Communications Option Boards.
Communications mode
Host Link
Serial PLC Links
Serial Gateway
No-protocol
1:N NT Link
1:1 NT Link
1:1 Link Master
1:1 Link Slave
Note
(1) The NT-AL001-E Link Adapter can be used to convert between RS-232C and RS-422A/485 to en-
able 1:N communications.
(2) Use 4-wire connections between Link Adapters.
Models of Serial Communications Option Board
Model
CP1W-CIF01
One RS-232C port
CP1W-CIF11
One RS-422A/485 port
Note The CP1W-CIF11 is a non-isolated board, so the maximum transmission distance is 50 m. For distances
over 50 m, use the RS-232C port on the CP1W-CIF01 and then connect through the NT-AL001-E Link
Adapter, which is isolated. Doing so will enable a maximum transmission distance of 500 m.
Appendix F
RS-232C
CP1W-CIF01
1:1
1:N
(See note 1.)
YES
YES
(See note 2.)
YES
YES
YES
YES
YES
YES
YES
YES
YES
No
YES
No
YES
No
Port
1:1 4-wire
1:N 4-wire
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
No
YES
No
YES
No
Maximum transmission
distance
15 m
50 m (See note.)
RS-422A/485
CP1W-CIF11
1:1 2-wire
1:N 2-wire
No
No
YES
YES
YES
YES
YES
YES
YES
YES
YES
No
YES
No
YES
No
Connection method
Connector (D-sub, 9-pin female)
Terminal block (using ferrules)
581

Advertisement

Table of Contents
loading

Table of Contents