9.2.11 To connect the brine low pressure switch

EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04
3 Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat according to the applicable
legislation.
In any case, to prevent unnecessary tripping of the safety thermostat, we
recommend the following:
The safety thermostat is automatically resettable.
The safety thermostat has a maximum temperature variation rate of 2°C/min.
There is a minimum distance of 2  m between the safety thermostat and the
3‑way valve.
INFORMATION
ALWAYS configure the safety thermostat after it is installed. Without configuration,
the unit will ignore the safety thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/9+10) as the safety thermostat. Thus, the system can have EITHER preferential
kWh rate power supply OR a safety thermostat.
Depending on the applicable legislation, you might have to install a brine low
pressure switch (field supply).
NOTICE
Mechanical. We recommend to use a mechanical brine low pressure switch. If an
electrical brine low pressure switch is used, capacitive currents might disturb the
flow switch operation causing an error on the unit.
Q4L
X5M
9
Electrical installation
|
Installer reference guide