Daikin Altherma 3 WS EWSAH06UD 9W Series Installer's Reference Manual page 264

Hide thumbs Also See for Altherma 3 WS EWSAH06UD 9W Series:
Table of Contents

Advertisement

10/11
Field settings table
Breadcrumb
Field code
Setting name
9.I
[B-03]
--
9.I
[B-04]
--
9.I
[C-00]
--
9.I
[C-01]
--
9.I
[C-02]
Is an external backup heat source connected?
9.I
[C-03]
Bivalent activation temperature.
9.I
[C-04]
Bivalent hysteresis temperature.
9.I
[C-05]
What is the thermo request contact type for the main zone?
9.I
[C-06]
What is the thermo request contact type for the add. zone?
9.I
[C-07]
What is the unit control method in space operation?
9.I
[C-08]
Which type of external sensor is installed?
9.I
[C-09]
What is the required alarm output contact type?
9.I
[C-0A]
--
9.I
[C-0B]
Brine pressure switch present?
9.I
[D-00]
Which heaters are permitted if prefer. kWh rate PS is cut?
9.I
[D-01]
Contact type of preferential kWh rate PS installation?
9.I
[D-02]
Which type of DHW pump is installed?
9.I
[D-03]
Leaving water temperature compensation around 0°C.
9.I
[D-04]
Is a demand PCB connected?
9.I
[D-05]
Is the pump allowed to run if prefer. kWh rate PS is cut?
9.I
[D-07]
--
9.I
[D-08]
Is an external kWh meter used for power measurement?
9.I
[D-09]
Is an external kWh meter used for power measurement?
9.I
[D-0A]
--
9.I
[D-0B]
--
9.I
[E-00]
Which type of unit is installed?
9.I
[E-01]
Which type of compressor is installed?
9.I
[E-02]
What is the indoor unit software type?
9.I
[E-03]
What kind of heater?
9.I
[E-04]
Is the power saving function available on the outdoor unit?
9.I
[E-05]
Can the system prepare domestic hot water?
9.I
[E-06]
Is a DHW tank installed in the system?
9.I
[E-07]
What kind of DHW tank is installed?
9.I
[E-08]
Power saving function for outdoor unit.
9.I
[E-09]
--
9.I
[E-0B]
Is a bi-zone kit installed?
9.I
[E-0C]
--
9.I
[E-0D]
--
9.I
[E-0E]
--
9.I
[F-00]
Pump operation allowed outside range.
9.I
[F-01]
Above which outdoor temperature is cooling allowed?
9.I
[F-02]
--
9.I
[F-03]
--
9.I
[F-04]
--
9.I
[F-05]
--
9.I
[F-09]
Pump operation during flow abnormality.
9.I
[F-0A]
--
9.I
[F-0B]
Close shut-off valve during thermo OFF?
9.I
[F-0C]
Close shut-off valve during cooling?
9.I
[F-0D]
What is the pump operation mode?
└─ Waterloop freezing temperature
4P675763-1 - 2021.10
Range, step
Default value
0
0
0
0
R/W
0: No
1: Bivalent
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step 1°C
3°C
R/W
0: -
1: 1 contact
2: 2 contacts
R/W
0: -
1: 1 contact
2: 2 contacts
R/W
0: LWT control
1: Ext RT control
2: RT control
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
0: Normally open
1: Normally closed
0
R/W
0: Not present
1: Present
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
R/W
0: No
1: Active open
2: Active closed
3: Safety thermostat
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
R/W
0: No
1: Pwr consmp ctrl
R/W
0: Forced off
1: As normal
0
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
0
2
R/O
0~5
5: GSHP
R/O
1
R/O
0: Reversible (*1)
1: Heating only (*2)
R/O
4: 9W
R/O
0: No
1: Yes
R/W
0: No
1: Yes
R/O
0: No
1: Yes
R/O
1: Integrated
R/O
0: disabled
1: Enabled
1
R/O
0
0
0
0
R/W
0: Disabled
1: Enabled
R/W
10~35°C, step: 1°C
20°C
3
5
0
0
R/W
0: Disabled
1: Enabled
0
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
0: Continuous
1: Sample
2: Request
Installer setting at variance with
default value
Date