Daikin Altherma 3 WS EWSAH06UD 9W Series Installer's Reference Manual page 197

Hide thumbs Also See for Altherma 3 WS EWSAH06UD 9W Series:
Table of Contents

Advertisement

Balancing
EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04
#
Code
[9.5.2]
[7-06]
NOTICE
Activating Compressor forced off mode will NOT stop or prevent the central
water loop pump from operating in the following conditions:
The Water loop valve test run has been started
Passive cooling is active
Priorities
For systems with an integrated domestic hot water tank.
#
[9.6.1]
[5‑02]
[9.6.2]
[5‑03]
Timers
For simultaneous space and domestic hot water operation request.
[8-02]: Anti-recycle timer
1
0
1
0
[8-01]
Activation of the Compressor forced off
mode:
0: disabled
1: enabled
Code
Space heating priority: Defines
whether backup heater will assist the heat
pump during domestic hot water operation.
For optimal operation and lowest power
consumption, it is strongly recommended to
keep the default setting (0).
If the backup heater operation is limited
([4‑00]=0) and the outdoor temperature is
lower than setting [5‑03], the domestic hot
water will not be heated with the backup
heater.
Priority temperature: Used for
calculation of anti-recycling timer. If [5‑02]=1, it
defines the outdoor temperature below which
the backup heater will assist during domestic
hot water heating.
[5‑01] Equilibrium temperature and [5‑03]
Space heating priority temperature are related
to backup heater. So, you must set [5‑03] equal
or a few degrees higher than [5‑01].
t
[8-02]
11
Configuration
|
Description
Description
Installer reference guide
197