Heat pump convectors – Multiple rooms
EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04
▪
For more information about connecting the electrical wiring to the unit, see
"9.2 Overview
of
4
actuators" [
89].
▪
For each room, a shut-off valve (field supplied) is installed to avoid leaving water
supply when there is no heating or cooling demand.
▪
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed.
▪
The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the indoor unit.
▪
The room thermostats are connected to the shut-off valves, but do NOT have to
be connected to the indoor unit. The indoor unit will supply leaving water all the
time, with the possibility to program a leaving water schedule.
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
Benefits
Compared with underfloor heating or radiators for one room:
▪
Comfort. You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Setup
C
B
a
a
A Main leaving water temperature zone
B Room 1
C Room 2
a Heat pump convectors + controllers
b Remote outdoor sensor