Field settings table
Breadcrumb
Field code
Setting name
9.1.6
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.1.7
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
└─ Additional zone
9.1.8.1
[2-0D]
Emitter type
9.1.8.3
Setpoint mode
9.1.8.4
Schedule
9.1.9
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-02]
High ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
9.1.A
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
9.1.A
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
9.1.A
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
9.1.A
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
└─ Tank
9.1.B.1
[6-0D]
Heat up mode
9.1.B.2
[6-0A]
Comfort setpoint
9.1.B.3
[6-0B]
Eco setpoint
9.1.B.4
[6-0C]
Reheat setpoint
9.1.B.5
[6-08]
Reheat hysteresis
└─ Domestic hot water
9.2.1
[E-05]
Domestic hot water
[E-06]
[E-07]
9.2.2
[D-02]
DHW pump
└─ Back up heater
9.3.1
[E-03]
BUH type
9.3.2
[5-0D]
Voltage
9.3.6
[5-00]
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
9.3.7
[5-01]
Equilibrium temperature
9.3.8
[4-00]
Operation
9.3.9
[4-07]
Maximum BUH capacity
Installer settings
└─ Emergency
9.5.1
[4-06]
Emergency
9.5.2
[7-06]
Compressor forced off
└─ Balancing
9.6.1
[5-02]
Space heating priority
9.6.2
[5-03]
Priority temperature
9.6.4
[8-02]
Anti-recycle timer
9.6.5
[8-00]
Minimum running timer
(*1) *X*_(*2) *H*
Range, step
Default value
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
22°C
[2-0C]=1
35°C
[2-0C]=2
25°C
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
22°C
[2-0C]=1
35°C
[2-0C]=2
25°C
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
45°C
[2-0C]=1
55°C
[2-0C]=2
65°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-40°C
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
30~[6-0E]°C, step: 1°C
60°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
2~20°C, step: 1°C
10°C
R/W
No DHW
Integrated
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
R/O
4: 9W
R/W
0: 230V, 1~
2: 400V, 3~
R/W
0: No
1: Yes
R/W
-15~35°C, step: 1°C
0°C
R/W
0: Disabled
1: Enabled
2: Only DHW
R/W
[5-0D]=2: 0~9 kW, step 1 kW
9 kW
[5-0D]≠2: 0~6 kW, step 1 kW
6 kW
R/W
0: Manual
1: Automatic (normal SH/ DHW ON)
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/W
-15~35°C, step: 1°C
0°C
R/W
0~10 hour, step: 0,5 hour
0,5 hour
R/W
0~20 min, step 1 min
1 min
5/11
Installer setting at variance with
default value
Date
Value
4P675763-1 - 2021.10