6.6.2 Power limitation activated by digital inputs

EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04
Set the power consumption control settings in [9.9] via the user interface (see
"Power consumption
-
Select continuous limitation mode
-
Select the type of limitation (power in kW or current in A)
-
Set the desired power limitation level
Power limitation is also useful in combination with an energy management system.
The power or current of the entire Daikin system is limited dynamically by digital
inputs (maximum four steps). Each power limitation level is set via the user
interface by limiting one of the following:
Current (in A)
Power input (in kW)
The energy management system (field supply) decides the activation of a certain
power limitation level. Example: To limit the maximum power of the entire house
(lighting, domestic appliances, space heating...).
B
a
5
4
3
A8P
2
1
b
A
A Indoor unit
B Energy management system
a Power limitation activation
b Backup heater
P
i
a
DI1
DI3
DI4
P
Power input
i
t Time
DI Digital inputs (power limitation levels)
a Power limitation active
b Actual power input
Setup
Demand PCB (option EKRP1AHTA) needed.
Maximum four digital inputs are used to activate the corresponding power
limitation level:
-
DI1 = strongest limitation (lowest energy consumption)
-
DI4 = weakest limitation (highest energy consumption)
4
control" [
 200]):
b
t
6
Application guidelines
|
Installer reference guide
53