Specific installer safety instructions
Installer reference guide
18
WARNING
Due to the presence of glycol, corrosion of the system is possible. Uninhibited glycol
will turn acidic under the influence of oxygen. This process is accelerated by the
presence of copper and high temperatures. The acidic uninhibited glycol attacks
metal surfaces and forms galvanic corrosion cells that cause severe damage to the
system. Therefore it is important that:
the water treatment is correctly executed by a qualified water specialist,
a glycol with corrosion inhibitors is selected to counteract acids formed by the
oxidation of glycols,
no automotive glycol is used because their corrosion inhibitors have a limited
lifetime and contain silicates which can foul or plug the system,
galvanized pipes are NOT used in glycol systems since the presence may lead to
the precipitation of certain components in the glycol's corrosion inhibitor.
Electrical installation (see
DANGER: RISK OF ELECTROCUTION
WARNING
Electrical wiring connection method MUST be in accordance with the instructions
from:
This manual. See
The wiring diagram, which is delivered with the unit, located on the inside of the
indoor unit switch box cover. For a translation of its legend, see
diagram: Indoor
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
"9 Electrical
installation" [
4
"9 Electrical
installation" [
4
unit" [
 245].
4
 86])
 86].
"17.2  Wiring
Daikin Altherma 3 WS
4P675765-1 – 2022.04