Installation of EKRP1AHTA is required.
3 Fix the cable with cable ties to the cable tie mountings.
6.13
To connect the safety thermostat
(normally closed contact)
Wires: 2×0.75 mm²
Safety thermostat contact: 16 V DC detection (voltage
supplied by PCB)
[9.8.1]=3 (Benefit kWh power supply = Safety
thermostat)
1 Open the following (see
"4.2.1 To open the indoor
1 Top panel
2 User interface panel
3 Installer switch box cover
2 Connect the safety thermostat (normally closed) cable to the
appropriate terminals as shown in the illustration below.
EGSAH/X06+10UD
Daikin Altherma 3 GEO
4P598591-1C – 2023.02
1
a
unit" [ 4  6]):
1
3 Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety
thermostat, we recommend the following:
▪ The safety thermostat is automatically resettable.
▪ The safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ There is a minimum distance of 2 m between the safety
thermostat and the 3‑way valve.
INFORMATION
ALWAYS configure the safety thermostat after it is
installed. Without configuration, the unit will ignore the
safety thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat.
preferential kWh rate power supply OR a safety
3
2
thermostat.
6.14
To connect the brine low pressure
switch
Depending on the applicable legislation, you might have to install a
brine low pressure switch (field supply).
NOTICE
Mechanical. We recommend to use a mechanical brine
low pressure switch. If an electrical brine low pressure
switch is used, capacitive currents might disturb the flow
switch operation causing an error on the unit.
NOTICE
Before disconnecting. If you want to remove or
disconnect the brine low pressure switch, first set [C‑0B]=0
(brine low pressure switch not installed). If not, this causes
an error.