Daikin Altherma 3 WS EWSAH06UD 9W Series Installer's Reference Manual page 14

Hide thumbs Also See for Altherma 3 WS EWSAH06UD 9W Series:
Table of Contents

Advertisement

2
|
General safety precautions
Installer reference guide
14
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
category III condition, MUST be installed in the fixed wiring.
WARNING
ONLY use copper wires.
Make sure the field wiring complies with the applicable legislation.
All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the
terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.
Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself MUST be as such that the current-carrying wires are
tautened before the earth wire is in case the power supply is pulled loose from
the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma 3 ws ewsax06ud 9w seriesEwsah06ud 9w seriesEwsax06ud 9w seriesAltherma 3 ws

Table of Contents