1× 4× Daikin website (publicly accessible). ENERG ENERG ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). Online tools In addition to the documentation set, some online tools are available 1× 1×...
(example: open flames, an operating gas appliance or an operating electric heater). WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 –...
4 6]): 1 User interface panel 2 Front panel 5 Open the installer switch box as follows: 2 Remove the insulation from the shut-off valves by cutting the cable ties. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Page 8
6 Unlink the connectors that run from the hydro module to the main switch box or other locations. Route the wires through the grommets of the upper hydro module cover. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
1° 1° 0° NOTICE To avoid structural damage on unit, ONLY move the unit Water drain valve when levelling feet are at their lowest position. Central water loop drain valve EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Install air purge valves at all local high points. this case, it is the responsibility of the installer to install a filter on the central water loop side of the system. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
3 Close all water taps after all air is purged. 4 Check for water leaks. 5 Manually operate the field-installed pressure relief valve to ensure a free water flow through the discharge pipe. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
[9.9.1]=3 (Power consumption Thermostat for passive "5.14 To connect the thermostat for control = Current sensor) cooling" [ 4 22]. cooling passive [9.9.E] Current sensor offset adapter" [ 4 22]. LAN adapter "5.15 LAN connections EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
(1N~ or 3N~) C5: Power supply for the rest of the unit — Preferential kWh rate power supply with (1N~) separate normal kWh rate power supply NOT ALLOWED Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Page 15
Detail C1: Factory-mounted power supply cable 2× Wires: 3N+GND, OR 1N+GND Maximum running current: Refer to name plate on unit. 1× Connect the factory-mounted power supply cable to a 1N~ or 3N~ power supply. 1× EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
2 Connect the valve control cable to the appropriate terminals as shown in the illustration below. NOTICE Wiring is different for a NC (normally closed) valve and a NO (normally open) valve. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
(field supply) so that they are double insulated. Wires connected to the alarm output Wire between the installer 14a 21 switch box and main switch Installation of EKRP1HBAA is required. Cable sleeve (field supply) Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
3 Fix the cable with cable ties to the cable tie mountings. To connect the space cooling/ heating ON/OFF output Wires: (2+1)×0.75 mm² Maximum load: 3.5 A, 250 V AC — unit" [ 4 6]): 1 Open the following (see "3.2.1 To open the indoor EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
4 Main switch box cover appropriate terminals as shown in the illustration below. 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
If an electrical low pressure switch is used, capacitive currents might disturb the flow switch operation causing an error on the unit. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
▪ Integration of the heat pump system in a Smart Grid application Cut loop wires coming from A16P/X13A/1+4 (factory mounted) Splicing connectors (field supply) Wires of the central water loop low pressure switch cable (field supply) Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Unit control method On the user interface, make sure to set Solar inverter/ 0.75~1.5 mm Depends on 100 m [2.9]=2 (Control = Room thermostat) energy application management system + 230 V AC detection voltage (X1A) EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Power line (field supply) INFORMATION It is recommended to connect the LAN adapter to the router directly. Depending on the wireless bridge or power line adapter model, the system might not function properly. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
3 For the system to run in the "Recommended ON" operation mode (Smart Grid application), connect the digital outputs of the solar inverter/energy management system to LAN adapter digital inputs X1A/1+2 LAN. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
"6.1.1 To access the most used ▪ Afterwards. If necessary, you can make changes to the configuration in the menu structure or the overview settings. User pin code The User pin code is 0000. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
If required, you can afterwards configure more settings. You can change all these settings via the menu structure. Protective functions The unit is equipped with the following protective functions: EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
The backup heater is adapted to be connected to most common European electricity grids. The type of backup heater can be viewed but not changed. Code Description [9.3.1] [E‑03] ▪ 4: 9W Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Control Emitter type Define how the operation of the unit is controlled. For more info about this functionality, see "6.2.5 Configuration zone" [ 4 29]. wizard: Main EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Because it reacts more [5.9] [6-00] Heat pump ON hysteresis quickly, it prevents high rises and drops of the indoor temperature ▪ 2°C~40°C and water temperature at tap points. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Example to equally increase the leaving water temperature for all ambient temperatures. Examples Weather-dependent curve when slope is selected: Weather-dependent curve when offset is selected: EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Main zone – Cooling The following table describes how to fine-tune the weather- dependent curve of a zone or tank: [2.4] Main zone > Setpoint Weather dependent mode Additional zone – Heating Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
The installer can fill in his contact number here. Water loop valve opening, Duration: [3‑0B] Code Description ▪ 30~120 minutes, step 30 minutes [8.3] Number that users can call in case of problems. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
[9.B] Sensors External sensor Ext. amb. sensor offset Averaging time [9.C] Bivalent Bivalent Boiler efficiency Temperature Hysteresis INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
▪ Between the indoor unit and the valves (if applicable) ▪ Between the indoor unit and the room thermostat (if applicable) The system is properly earthed and the earth terminals are tightened. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
4 26]. change the user permission 2 Select OK to confirm. 2 Go to [A.2]: Commissioning > Actuator test run. 3 Select a test from the list. Example: Pump. Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
9 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). Piping diagram: Indoor unit...
PC=power circuit) (1) Main power connection (1) Main power connection Backup heater control PCB For preferential kWh rate power For preferential kWh rate power Inverter PCB supply supply * Demand PCB EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Page 40
Normally closed Normally open Normally open Safety thermostat contact: 16 V Safety thermostat contact: DC detection (voltage supplied 16 V DC detection (voltage by PCB) supplied by PCB) Shut-off valve Shut-off valve Installation manual EWSAH/X06DA9W Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Page 41
Power limitation demand input 3 FIELD SUPPLY A8P: X801M: 3-5 signal 2 core Power limitation demand input 4 Router for LAN adapter A8P: X801M: 4-5 A15P: X4A signal ethernet 4D137622 EWSAH/X06DA9W Installation manual Daikin Altherma 3 WS 4P675759-1 – 2021.10...
Page 44
4P675759-1 0000000. 4P675759-1 2021.10 Verantwortung für Energie und Umwelt...