11
|
Configuration
Installer reference guide
176
#
Code
[4.4]
[7‑02]
[4.4]
[7‑02]
NOTICE
NOT configuring the system in the following way can cause damage to the heat
emitters. If there are 2 zones, it is important that in heating:
▪
the zone with the lowest water temperature is configured as the main zone, and
▪
the zone with the highest water temperature is configured as the additional zone.
Description
▪
0: Single zone
Only one leaving water temperature zone:
a
a Main LWT zone
▪
1: Dual zone
Two leaving water temperature zones. The
main leaving water temperature zone consists
of the higher load heat emitters and a mixing
station to achieve the desired leaving water
temperature. In heating:
a
c
b
a Additional LWT zone: Highest temperature
b Main LWT zone: Lowest temperature
c Mixing station
EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04